(224) 955-1644
Hammond ManufacturingAuthorized partner store
1182W12 1000 VA toroidal power transformer with 12V secondary leads

Hammond 1182W12 1000 VA Toroid Transformer, 12V @ 83.4A Dual Secondary

Hammond Manufacturing|

MPN: 1182W12

|

UPC: 623980240428

In Stock
$179.91

Ships from and sold by A5 IT

Ground Shipping · $28.05Arrives by Monday, Oct 26
Order within 3h 39m to get it by Monday, Oct 26
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 1000 VA toroidal power transformer, open center
  • Secondary: 24V C.T. @ 41.7A series or 12V @ 83.4A parallel
  • Dual 117/234 VAC primary, 50/60 Hz operation
  • 2.20% voltage regulation (series table)
  • Includes two rubber washers, steel mounting washer and 3/8-16 x 3.50" bolt with nut
  • #16 TEW primary and #10 TEW secondary leads, 8"-9" long
  • Hi-pot 4000V primary to secondary; Class B (130 degree C) materials
  • UL recognized (E207860), CSA certified (209651), RoHS and REACH compliant

The 1182W12 is a 1000 VA toroidal power transformer from the 1182 Series for equipment designers who need a high-current 12 V or 24 V centre-tapped AC source. It runs from a dual 117/234 VAC primary at 50/60 Hz and carries two 12 V secondaries rated 41.70 A each.

With the secondaries in series the output is 24V C.T. @ 41.7A; in parallel it is 12V @ 83.4A. The series table lists voltage regulation at 2.20%. The units are designed to have all windings engaged, either series or parallel connected, or connected as an autotransformer, and a connection sheet is included with the transformer.

This is an open-center toroid (dimension reference L-1). It is supplied with two 0.093" T x 4.75" OD rubber washers, one 16GA x 4.30" OD steel mounting washer, and one 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut. Primary leads are #16 TEW and secondary leads are #10 TEW, all brought out 8"-9" and stripped 0.5" minimum. The drawing gives a weight of 16.29 lbs +/- 4%, with a shipping weight of 16.5 lbs (7.48 kg).

The toroid core shape provides a low profile, lightweight, cool running, high efficiency transformer with low stray magnetic flux leakage (low EMI). It uses Class B (130 degree C) materials and is hi-pot tested at 4000V, 60Hz for 1 second primary to secondary and 600V primary to primary and secondary to secondary. The 1182 Series is UL recognized (file #E207860) and CSA certified (file #209651); the 1182W12 is RoHS and REACH compliant. Because toroids draw high inrush current on switch-on, use a slow-blow fuse, time delayed breaker or soft start circuitry.

Ideal For

  • High-current 12V or 24V C.T. AC supplies
  • Equipment powered from 117 VAC or 234 VAC lines
  • Low-EMI power supplies in electronic equipment
  • Replacement for older 182 Toroid Series units

Mounting

Supplied HardwareTwo 0.093" T x 4.75" OD rubber washers; one 16GA x 4.30" OD steel mounting washer; one 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut
Series Hardware NoteTwo neoprene rubber insulating pads, one metal centering washer and all mounting hardware

Overview

Series1182 Series
ReplacesOlder 182 Toroid Series
Power Rating1000 VA
Product TypePower transformer, toroid
Toroid CenterOpen
Short DescriptionTOROID,1000VA, 50/60HZ, 12/12V
Dimension ReferenceL-1
Included DocumentationConnection sheet included with transformer

Electrical

PrimaryDual 117/234 VAC primary, 50/60 Hz operation
PolarityBLK, BRN, RED and GRY additive
Inrush NoteHigh magnetizing current when initially energized; consider a slow-blow fuse, time delayed circuit breaker or soft start circuitry
Primary Windings2x 117V 50/60Hz (BLK-WHT, BRN-ORN)
Secondary Windings2x 12V @ 41.70A (RED-BLU, GRY-YEL)
Winding ConnectionAll windings engaged (series or parallel connected) or connected as an autotransformer
Secondary (RMS) Series24V C.T. @ 41.7A
Dual Or Single SecondaryDual
Hi-Pot Primary - Primary600V, 60Hz, 1 sec
Secondary (RMS) Parallel12V @ 83.4A
Hi-Pot Test (Series Spec)4,000 VAC RMS between primary & secondary
Hi-Pot Primary - Secondary4000V, 60Hz, 1 sec
Hi-Pot Secondary - Secondary600V, 60Hz, 1 sec
% Voltage Regulation (Part Page)2
% Voltage Regulation (Series Table)2.20%
Secondary No-Load Voltage Test Conditions@ 117V, 60Hz BLK & BRN to WHT & ORN, or @ 234V, 50Hz BLK to ORN (connect BRN & WHT)

Identifiers

UPC623980240428
UNSPSC39121301
Label Code1A1000A000C012012
Country Of OriginMade in Canada

Packaging & Shipping

Shipping Weight16.5 lbs (7.48 kg)
Weight (Drawing)16.29 lbs +/- 4%

Construction & Finish

Core TypeToroid
Lead LengthAll leads out 8"-9" and stripped 0.5" min
Primary Leads#16 TEW
Secondary Leads#10 TEW
Insulation ClassClass B (130 degree C) materials
Leads (Series Spec)Minimum 8" long flexible leads

Compliance & Certifications

ULUL recognized to UL 5085-1 and UL 5085-2, UL file #E207860
CSACSA certified to C22.2 #66.1-6 and C22.2 #66.2-6, CSA file #209651
IEC/ENSelf-declared evaluated to applicable sections of IEC/EN61558-1 (Second Edition 2005-09) and IEC/EN61558-2-4
RoHS CompliantYes
REACH CompliantYes

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What are the output ratings of the 1182W12?▾

Its two 12V @ 41.70A secondaries give 24V C.T. @ 41.7A when connected in series, or 12V @ 83.4A when connected in parallel.

Can it run on both 117 V and 234 V?▾

Yes. The dual 117V primaries are wired in parallel for 117 VAC or in series for 234 VAC, at 50/60 Hz.

What hardware is included?▾

Two 0.093" T x 4.75" OD rubber washers, one 16GA x 4.30" OD steel mounting washer, and one 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut.

What wire gauge are the leads?▾

Primary leads are #16 TEW and secondary leads are #10 TEW. All leads come out 8"-9" and are stripped 0.5" minimum.

What is the voltage regulation?▾

The 1182 Series ordering table lists 2.20% voltage regulation for the 1182W12.

How should the supply be protected?▾

Toroidal transformers can draw high magnetizing current at switch-on for up to about half a cycle, so a slow-blow fuse, time delayed circuit breaker or soft start circuitry is recommended.