Key Features

  • 25526 BTU/h (7475 W) at +95/+95 °F (+35/+35 °C)
  • 460V 50/60 Hz, 414-506V, 2843W, 5.18A running, 10A starting
  • Maintains NEMA 12 / IP 54; UL, cUL and CE
  • 1653 CFM internal and 627 CFM external airflow
  • 57.20 x 15.80 x 16.10 in (1453 x 401 x 409 mm), 226.2 lbs
  • Hot gas bypass valve minimizes heavy inrush currents
  • 3 mm condenser fin spacing for aggressive ambient air
  • Filterless, built-in condensate evaporator

The DTS3641CA460LG is the 460 V, 50/60 Hz, 25,000 BTU/H class model in the DTS 20,000-25,000 BTU/H indoor air conditioner series. Designed for side mounting on any enclosure surface where high capacity system cooling is required, it is aimed at large industrial enclosures on 460 V distribution.

Its rated cooling capacity is 25526 BTU/h (7475 W) at +95/+95 °F (+35/+35 °C), the highest in the four-model series table. Power consumption is 2843 W, with 5.18 A running current and 10 A starting current over a 414-506 V operating range, wired through a terminal block. A hot gas bypass valve prevents evaporator freeze up while minimizing heavy inrush currents on this large BTU/H unit.

Closed loop cooling recirculates clean enclosure air without mixing with contaminated ambient air. Unrestricted air capacity is 1653 CFM internal and 627 CFM external, with maximum clearance between warm inlet and cold outlet to reduce hot spots, and the condenser's 3 mm fin spacing protects against strongly contaminated and aggressive ambient air. The R-134a thermostat is adjustable from +77 to +113 °F (+25 to +45 °C), factory set to +95 °F (+35 °C), and accessible from inside the enclosure. Ambient air limits are +46 °F (+8 °C) to +131 °F (+55 °C); noise is 81 dB(A).

The DTS3641CA460LG measures 57.20 in (1453 mm) high, 15.80 in (401 mm) wide and 16.10 in (409 mm) deep, weighs 226.2 lbs (102.6 kg), and has a galvanized sheet steel case finished in RAL7035 light gray. It maintains NEMA 12 / IP 54, holds UL, cUL and CE approvals, is filterless with a built-in condensate evaporator, and includes the gasket, mounting kit, drilling template and condensate drain hose and clamp.

Ideal For

  • High capacity cooling for 460 V industrial enclosures
  • Side-mounted cooling for NEMA 12 control cabinets
  • Reducing hot spots in high heat-load enclosures
  • Cooling enclosures in strongly contaminated ambient air

Cooling

Filter MatFilterless
RefrigerantR-134a
Cooling MethodClosed loop - clean enclosure air recirculated without mixing with ambient air
Air CirculationContinuous, from high capacity fans; maximum clearance between warm inlet and cold outlet
Condensate DischargeCondensate evaporator (built in)
Hot Gas Bypass ValvePrevents evaporator freeze up while minimizing heavy inrush currents
Condenser Fin Spacing3 mm, for protection against strongly contaminated and aggressive ambient air
Air Capacity (Unrestricted)Internal circulation 1653 CFM; external circulation 627 CFM
Cooling Capacity (+95/+95 F, +35/+35 C)25526 BTU/h (7475 Watts)

Controls

ThermostatAccessible from inside enclosure
DiagnosticsSelf-diagnostics on startup; fault indication via LED light
Door ContactProvision for door contact allowing power down when enclosure door is opened
Factory Setting+95 °F / +35 °C
Adjustable Control Range+77 to +113 °F / +25 to +45 °C

Overview

SeriesDTS Series - 20,000-25,000 BTU/H Indoor Air Conditioner, Type 12, Side Mounting
Part NumberDTS3641CA460LG
Long DescriptionAC Unit 12-25000 BTU/H 460 V - NEMA 12 - LG
Short DescriptionAC UNIT 12-25000BTU-460V
Optional AccessoriesRemote door switches, filter kits, gasket kits, water condensate evaporator, condensate bottle

Dimensions

Depth16.10 in (409 mm)
Width15.80 in (401 mm)
Height57.20 in (1453 mm)
Unit Weight226.2 lbs (102.6 kg)
Size H X W X D57.2 in x 15.8 in x 16.1 in (1,453 mm x 401 mm x 409 mm)

Electrical

Line CordTerminal Block
Running Amps5.18A
Rated Voltage460V 50/60 Hz
Starting Current10A
Power Consumption2843W
Range Of Operation414-506V
EMI/RFI SuppressionMeets CE

Identifiers

UPC623980111377
UNSPSC39121301

Installation

MountingSide mounting on any enclosure surface
Drilling TemplateDrilling Template DTS 34/36x1, part number 885407019 (spare-part no. 18380000032), 1:1 printable format
Drilling Template Overall Dimensions1440 mm (56.69 in) x 350 mm (13.78 in)

Packaging & Shipping

IncludedGasket, mounting kit and template for enclosure cutout and drilling; condensate drain hose and clamp
Shipping Weight226.2 lbs (102.60 kg)

Construction & Finish

FinishRAL7035 Light Gray (LG)
Exterior CaseGalvanized sheet steel
Alternate Finish (GY)ANSI 61 Gray

Environmental & Protection

IP RatingIP 54
Noise Level81 dB(A)
Max Ambient Air Temp+131 °F (+55 °C)
Min Ambient Air Temp+46 °F (+8 °C)

Compliance & Certifications

ApprovalsUL, cUL and CE
NEMA RatingMaintains enclosure's NEMA 12 rating (Enclosures IP 54 / Nema 12)
RoHS CompliantYes
REACH CompliantYes

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What is the cooling capacity of the DTS3641CA460LG?▾

25526 BTU/h (7475 Watts) at +95/+95 °F (+35/+35 °C).

What electrical supply does it need?▾

460V 50/60 Hz, with an operating range of 414-506V. Running current is 5.18A and starting current is 10A; connection is by terminal block.

What are its dimensions?▾

57.20 in (1453 mm) high, 15.80 in (401 mm) wide and 16.10 in (409 mm) deep.

Does it keep the enclosure NEMA 12?▾

Yes. It maintains the enclosure's NEMA 12 rating and is IP 54, with UL, cUL and CE approvals.

What airflow does it provide?▾

Unrestricted air capacity is 1653 CFM internal circulation and 627 CFM external circulation.

What is included for installation?▾

A gasket, mounting kit and template for the enclosure cutout and drilling are included, plus a condensate drain hose and clamp.