Hammond DTS3061A460N3LG 2382 BTU/h 460V NEMA 3R/4 Outdoor Air Conditioner
Ships from and sold by A5 IT
Available on backorder — ships as soon as stock arrives
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- 460 V 50/60 Hz, 360-506 V range, 760 W, 0.76 A running current
- 2382 BTU/h (698 W) at +95/+95F (+35/+35C)
- NEMA 3R, 4 and IP56; UL, cUL and CE
- Ambient air rating +32°F (0°C) to +131°F (+55°C)
- Phase-sensitive three phase terminal block connection
- Galvanized sheet metal case, RAL7035 light gray; 64 lbs shipping
- Gasket, mounting kit and cutout/drilling template included
The DTS3061A460N3LG is the 460 V 50/60 Hz version of the DTS Series 2000-3000 BTU/H outdoor air conditioner, built for side mounting on any enclosure surface where spot cooling or low capacity cooling is required. It lets integrators and plant electricians cool outdoor-rated cabinets straight from a 460 V supply, including in very wet conditions.
Cooling is closed loop, so clean enclosure air never mixes with contaminated ambient air. Capacity is 2382 BTU/h (698 W) at +95/+95F (+35/+35C) per the series data sheet; the part description lists 2500 BTU. The R134a refrigerant charge is 400 g, and an expansion valve allows increased efficiency with less frequent compressor operation. Internal circulation is 191 CFM and external 88 CFM.
The unit operates from 360-506 V, consuming 760 W with 0.76 A running and 18 A starting current, wired to a terminal block. The manual cautions that on three phase (400V/460V) units the supply connections are phase sensitive, and the drilling template carries an extra cutout area marked for 400/460V units only.
The DTS3061A460N3LG has a galvanized sheet metal case in RAL7035 light gray. The part page lists a size of 26 in x 12 in x 14 in (660 x 305 x 356 mm) and a shipping weight of 64 lbs (29.03 kg); the series data sheet refers to the separate 460V datasheet for dimensions. Ratings are NEMA 3R, 4 and IP56, with UL, cUL and CE, for ambient air from +32°F (0°C) to +131°F (+55°C).
The gasket, mounting kit and template for cutout and drilling are included. The unit is filterless, and condensate is discharged directly through a drain hose and clamp on a 1/2" barb connection.
Ideal For
- 460 V outdoor NEMA 3R/4 enclosure cooling
- Spot cooling in very wet conditions
- Three phase industrial panel installations
Overview
| Mounting | Side mounting |
| Part Number | DTS3061A460N3LG |
| Cooling Type | Closed loop |
| Product Type | 2000-3000 BTU/H Outdoor Air Conditioner, DTS Series |
| Long Description | Air Conditioner 2500 BTU 460V |
| Short Description | AIR CONDIT 2500BTU 460V LG |
Dimensions
| Dimension Note | 460V dimensions not shown on series data sheet, see 460V datasheet |
| Nominal Size (H X W X D) | 26 in x 12 in x 14 in (660 mm x 305 mm x 356 mm) |
| Unit Weight (Series Data Sheet) | 61.7 lbs (28 kg) / 66.2 lbs (30 kg) |
| Drawing Heights (DTS 3041/61/81 460V 3-view Drawing) | 583.35 mm (22.97 in) / 569.03 mm (22.40 in) |
Electrical
| Line Cord | Terminal Block |
| Phase Note | On three phase connection (400V/460V) units the power supply connections are phase sensitive |
| Running Amps | 0.76 A |
| Rated Voltage | 460 V 50/60 Hz |
| Starting Current | 18 A |
| Power Consumption | 760 W |
| Range Of Operation | 360 - 506 V |
| EMI/RFI Suppression | Meets CE standard |
Accessories
| Available Accessories | Remote Door Switches, Filter Kits, Gasket Kits, Water Condensate Evaporator, Condensate Bottle |
Identifiers
| UPC | 623980468945 |
| UNSPSC | 40101701 |
Performance
| Control | Thermostat control |
| Noise Level | <64 dB (A) |
| Refrigerant | R134a |
| Expansion Valve | Permits increased efficiency through improved evaporator heat transfer and less frequent compressor operation |
| Factory Setting | +95F / +35C |
| Refrigerant Charge | 400 g |
| Adjustable Control Range | +50F..104F / +10C..+40C |
| Cooling Capacity (+95/+95F, +35/+35C) | 2382 BTU/h (698 W) |
| Air Capacity, External Circulation (Unrestricted) | 88 CFM |
| Air Capacity, Internal Circulation (Unrestricted) | 191 CFM |
Installation
| Template Note | Patterned cutout area on the drilling template is for 400/460V units only |
| Drilling Template | Drilling template DTS 30xx, part number 18380000007 |
Packaging & Shipping
| Included | Gasket, mounting kit, and template for cutout and drilling |
| Shipping Weight | 64 lbs (29.03 kg) |
| Scope Of Delivery | DTS cooling unit, cooling unit quick guide, accessory kit (seal, fastening material, electrical plug connector, etc.) |
Construction & Finish
| Finish | RAL7035 light gray (LG) |
| Colour Option | For ANSI 61 Gray replace LG with GY |
| Exterior Case | Galvanized sheet metal |
Environmental & Protection
| IP Rating | IP56 |
| Filter Mat | Filterless (aluminum, fleece and fluted filters possible with an additional adapter) |
| NEMA Rating | NEMA 3R, 4 |
| Suitability | Ideal for outdoor or very wet conditions |
| Max Ambient Air Temp | +131°F (+55°C) |
| Min Ambient Air Temp | +32°F (0°C) |
| Condensation Discharge | Condensate drain; direct discharge, drain hose and clamp, 1/2" barb connection |
Compliance & Certifications
| Standards | UL, cUL, and CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| Material Declaration | RoHS-compliant and free from silicone connections, PCT, asbestos, formaldehyde, cadmium and moisture-impairing substances |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What supply does the DTS3061A460N3LG require?▾
460 V 50/60 Hz, with a range of operation of 360-506 V. It consumes 760 W and draws 0.76 A running, 18 A starting.
Is the power connection phase sensitive?▾
Yes. The manual states that on three phase (400V/460V) units the power supply connections are phase sensitive and must be correct for proper operation.
What size is it?▾
The part page lists 26 in x 12 in x 14 in (660 mm x 305 mm x 356 mm). The series data sheet refers to the 460V datasheet for its dimensions.
What ratings does it carry?▾
NEMA 3R, 4 and IP56, with UL, cUL and CE approvals. It is also RoHS and REACH compliant.
What is the operating temperature range?▾
Ambient air from +32°F (0°C) to +131°F (+55°C).
Related Products
Save 31%DTS3061A230N3LG — Air Conditioner 2500 BTU 3R 230V LG
Hammond Manufacturing · DTS3061A230N3LG

DTS3081A115N4SS — AC Unit 2,500 BTU/H 115 V - NEMA 4x - 304 SS
Hammond Manufacturing · DTS3081A115N4SS

DTS3061A115N3LG — Air Conditioner 2500BTU 3R 115V LG
Hammond Manufacturing · DTS3061A115N3LG
Save 31%DTS3081A230N4SS — AC Unit 2,500 BTU/H 230 V - NEMA 4x - 304 SS
Hammond Manufacturing · DTS3081A230N4SS
Save 31%DTS3081A460N4SS — Air Conditioner 2500 BTU 460V SS
Hammond Manufacturing · DTS3081A460N4SS