(224) 955-1644
Hammond ManufacturingAuthorized partner store
DTS3081A460N4SS 460 V 304 stainless steel NEMA 4X side-mount enclosure air conditioner

Hammond DTS3081A460N4SS 2382 BTU/h 460V NEMA 4X Stainless Air Conditioner

Hammond Manufacturing|

MPN: DTS3081A460N4SS

|

UPC: 623980468952

Available on Backorder
$3,175.84

Ships from and sold by A5 IT

Available on backorder — ships as soon as stock arrives

Ground Shipping · $134.99Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 460 V 50/60 Hz, 360-506 V range, 760 W, 0.76 A running
  • Stainless steel body, 304 SS #4 brush finish
  • NEMA 4X; series complies with IP56 and NEMA 3R, 4, 4X; UL, cUL, CE
  • 2382 BTU/h (698 W) at +95/+95F (+35/+35C)
  • Phase-sensitive three phase terminal block connection
  • Ambient air rating +32°F (0°C) to +131°F (+55°C)
  • Gasket, mounting kit and cutout/drilling template included

The DTS3081A460N4SS is the 460 V stainless steel model in the DTS Series 2000-3000 BTU/H outdoor air conditioner range. Designed for side mounting on any enclosure surface where spot cooling or low capacity cooling is required, it pairs a stainless steel body with 460 V 50/60 Hz power for NEMA 4X cabinets in outdoor or very wet conditions.

Its closed loop cooling keeps enclosure air clean and separate from contaminated ambient air. The series data sheet rates it at 2382 BTU/h (698 W) at +95/+95F (+35/+35C), and the part description lists 2500 BTU. An R134a circuit with a 400 g charge and an expansion valve supports efficient operation with less frequent compressor cycling, while fans deliver 191 CFM internal and 88 CFM external circulation.

The DTS3081A460N4SS operates from 360-506 V, consuming 760 W with 0.76 A running and 18 A starting current, connected at a terminal block. The manual notes that three phase (400V/460V) units are phase sensitive at the supply connections, and the drilling template has an additional cutout area marked for 400/460V units only.

The finish is 304 Stainless Steel #4 Brush. The part page lists a size of 26 in x 12 in x 14 in (660 x 305 x 356 mm) and a shipping weight of 68 lbs (30.84 kg). The series complies with IP56 and NEMA 3R, 4, 4X and carries UL, cUL and CE; the part description lists NEMA 4x. Ambient air range is +32°F (0°C) to +131°F (+55°C).

The gasket, mounting kit and cutout/drilling template are included. It operates filterless, with condensate discharged through a drain hose and clamp on a 1/2" barb connection.

Ideal For

  • 460 V stainless NEMA 4X enclosures
  • Outdoor or very wet industrial locations
  • Three phase side-mounted cabinet cooling

Overview

MountingSide mounting
Part NumberDTS3081A460N4SS
Cooling TypeClosed loop
Product Type2000-3000 BTU/H Outdoor Air Conditioner, DTS Series
Long DescriptionAir Conditioner 2500 BTU 460V SS
Short DescriptionAIR CONDIT 2500BTU 460V SS

Dimensions

Dimension Note460V dimensions not shown on series data sheet, see 460V datasheet
Nominal Size (H X W X D)26 in x 12 in x 14 in (660 mm x 305 mm x 356 mm)
Unit Weight (Series Data Sheet)61.7 lbs (28 kg) / 66.2 lbs (30 kg)
Drawing Heights (DTS 3041/61/81 460V 3-view Drawing)583.35 mm (22.97 in) / 569.03 mm (22.40 in)

Electrical

Line CordTerminal Block
Phase NoteOn three phase connection (400V/460V) units the power supply connections are phase sensitive
Running Amps0.76 A
Rated Voltage460 V 50/60 Hz
Starting Current18 A
Power Consumption760 W
Range Of Operation360 - 506 V
EMI/RFI SuppressionMeets CE standard

Accessories

Available AccessoriesRemote Door Switches, Filter Kits, Gasket Kits, Water Condensate Evaporator, Condensate Bottle

Identifiers

UPC623980468952
UNSPSC40101701

Performance

ControlThermostat control
Noise Level<64 dB (A)
RefrigerantR134a
Expansion ValvePermits increased efficiency through improved evaporator heat transfer and less frequent compressor operation
Factory Setting+95F / +35C
Refrigerant Charge400 g
Adjustable Control Range+50F..104F / +10C..+40C
Cooling Capacity (+95/+95F, +35/+35C)2382 BTU/h (698 W)
Air Capacity, External Circulation (Unrestricted)88 CFM
Air Capacity, Internal Circulation (Unrestricted)191 CFM

Installation

Template NotePatterned cutout area on the drilling template is for 400/460V units only
Drilling TemplateDrilling template DTS 30xx, part number 18380000007

Packaging & Shipping

IncludedGasket, mounting kit, and template for cutout and drilling
Shipping Weight68 lbs (30.84 kg)
Scope Of DeliveryDTS cooling unit, cooling unit quick guide, accessory kit (seal, fastening material, electrical plug connector, etc.)

Construction & Finish

BodyStainless steel body
Finish304 Stainless Steel #4 Brush

Environmental & Protection

IP RatingIP56
Filter MatFilterless (aluminum, fleece and fluted filters possible with an additional adapter)
NEMA RatingNEMA 4X (part description); series: NEMA 3R, 4, 4X
SuitabilityIdeal for outdoor or very wet conditions
Max Ambient Air Temp+131°F (+55°C)
Min Ambient Air Temp+32°F (0°C)
Condensation DischargeCondensate drain; direct discharge, drain hose and clamp, 1/2" barb connection

Compliance & Certifications

StandardsUL, cUL, and CE
RoHS CompliantYes
REACH CompliantYes
Material DeclarationRoHS-compliant and free from silicone connections, PCT, asbestos, formaldehyde, cadmium and moisture-impairing substances

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What supply does the DTS3081A460N4SS need?▾

460 V 50/60 Hz, with a range of operation of 360-506 V. It consumes 760 W and draws 0.76 A running, 18 A starting.

Is the supply connection phase sensitive?▾

Yes. On three phase (400V/460V) units the power supply connections are phase sensitive; connect them correctly or the unit will not operate properly.

What is it made of?▾

A stainless steel body with a 304 Stainless Steel #4 Brush finish.

How large and heavy is it?▾

The part page lists 26 in x 12 in x 14 in (660 mm x 305 mm x 356 mm) and a shipping weight of 68 lbs (30.84 kg).

What ratings does it have?▾

The part description lists NEMA 4x; the series complies with IP56 and NEMA 3R, 4, 4X, with UL, cUL and CE.