Hammond DTS3081A230N4SS 2382 BTU/h 230V NEMA 4X Stainless Air Conditioner
Ships from and sold by A5 IT
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- 230 V 50/60 Hz, 198-253 V range, 760 W, 1.52 A running
- Stainless steel body, 304 SS with #4 brush finish
- NEMA 4X; series complies with IP56 and NEMA 3R, 4, 4X
- 2382 BTU/h (698 W) closed loop cooling
- Operates in +32°F (0°C) to +131°F (+55°C) ambient air
- UL, cUL and CE; EMI/RFI suppression meets CE
- Includes gasket, mounting kit and cutout/drilling template
The DTS3081A230N4SS is a 230 V 50/60 Hz stainless steel air conditioner for outdoor and very wet locations. As part of the DTS Series 2000-3000 BTU/H outdoor range it side mounts on any enclosure surface where spot cooling or low capacity cooling is required, making it a fit for stainless NEMA 4X cabinets used by OEMs and facilities teams.
Closed loop cooling recirculates clean enclosure air without mixing it with contaminated ambient air. The unit is rated 2382 BTU/h (698 W) at +95/+95F (+35/+35C), described on the part page as 2,500 BTU/H, and uses R134a with a 400 g charge. Its expansion valve permits increased efficiency, and high capacity fans provide 191 CFM internal and 88 CFM external circulation.
This model operates on 198-253 V with 760 W power consumption, 1.52 A running current and 18 A starting current, connected at a terminal block. EMI/RFI suppression meets the CE standard.
- Drawing dimensions 511.9 mm (20.15 in) H x 255.3 mm (10.05 in) W x 273.6 mm (10.77 in) D
- Shipping weight 50 lbs (22.68 kg)
- Stainless steel body, 304 Stainless Steel #4 Brush
- NEMA 4x per part description; series IP56, NEMA 3R, 4, 4X
- UL, cUL and CE
Ambient air range for the DTS3081A230N4SS is +32°F (0°C) to +131°F (+55°C). It is filterless, discharges condensate through a drain hose and clamp on a 1/2" barb connection, and ships with its gasket, mounting kit and cutout/drilling template.
Ideal For
- Stainless NEMA 4X enclosures on 230 V 50/60 Hz
- Outdoor or very wet locations
- Spot cooling of control cabinets
Overview
| Mounting | Side mounting |
| Part Number | DTS3081A230N4SS |
| Cooling Type | Closed loop |
| Product Type | 2000-3000 BTU/H Outdoor Air Conditioner, DTS Series |
| Long Description | AC Unit 2,500 BTU/H 230 V - NEMA 4x - 304 SS |
| Short Description | AIR CONDIT 2500BTU N4 230V SS |
Dimensions
| Drawing Dimensions (H X W X D) | 511.9 mm (20.15 in) x 255.3 mm (10.05 in) x 273.6 mm (10.77 in) |
| Unit Weight (Series Data Sheet) | 61.7 lbs (28 kg) / 66.2 lbs (30 kg) |
Electrical
| Line Cord | Terminal Block |
| Running Amps | 1.52 A |
| Rated Voltage | 230 V 50/60 Hz |
| Starting Current | 18 A |
| Power Consumption | 760 W |
| Range Of Operation | 198-253 V |
| EMI/RFI Suppression | Meets CE standard |
Accessories
| Available Accessories | Remote Door Switches, Filter Kits, Gasket Kits, Water Condensate Evaporator, Condensate Bottle |
Identifiers
| UPC | 623980009117 |
| UNSPSC | 40101701 |
Performance
| Control | Thermostat control |
| Noise Level | <64 dB (A) |
| Refrigerant | R134a |
| Expansion Valve | Permits increased efficiency through improved evaporator heat transfer and less frequent compressor operation |
| Factory Setting | +95F / +35C |
| Refrigerant Charge | 400 g |
| Adjustable Control Range | +50F..104F / +10C..+40C |
| Cooling Capacity (+95/+95F, +35/+35C) | 2382 BTU/h (698 W) |
| Air Capacity, External Circulation (Unrestricted) | 88 CFM |
| Air Capacity, Internal Circulation (Unrestricted) | 191 CFM |
Installation
| Drilling Template | Drilling template DTS 30xx, part number 18380000007 |
Packaging & Shipping
| Included | Gasket, mounting kit, and template for cutout and drilling |
| Shipping Weight | 50 lbs (22.68 kg) |
| Scope Of Delivery | DTS cooling unit, cooling unit quick guide, accessory kit (seal, fastening material, electrical plug connector, etc.) |
Construction & Finish
| Body | Stainless steel body |
| Finish | 304 Stainless Steel #4 Brush |
Environmental & Protection
| IP Rating | IP56 |
| Filter Mat | Filterless (aluminum, fleece and fluted filters possible with an additional adapter) |
| NEMA Rating | NEMA 4X (part description); series: NEMA 3R, 4, 4X |
| Suitability | Ideal for outdoor or very wet conditions |
| Max Ambient Air Temp | +131°F (+55°C) |
| Min Ambient Air Temp | +32°F (0°C) |
| Condensation Discharge | Condensate drain; direct discharge, drain hose and clamp, 1/2" barb connection |
Compliance & Certifications
| Standards | UL, cUL, and CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| Material Declaration | RoHS-compliant and free from silicone connections, PCT, asbestos, formaldehyde, cadmium and moisture-impairing substances |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What voltage is the DTS3081A230N4SS?▾
230 V 50/60 Hz, operating from 198-253 V. It consumes 760 W with 1.52 A running and 18 A starting current.
What is the construction?▾
A stainless steel body finished in 304 Stainless Steel #4 Brush.
Is it rated for wet environments?▾
The series is described as ideal for outdoor or very wet conditions and complies with IP56 and NEMA 3R, 4, 4X; the part description lists NEMA 4x.
What is the maximum ambient temperature?▾
+131°F (+55°C). The minimum is +32°F (0°C).
How is it powered?▾
Through a terminal block connection.
Related Products

DTS3081A115N4SS — AC Unit 2,500 BTU/H 115 V - NEMA 4x - 304 SS
Hammond Manufacturing · DTS3081A115N4SS
Save 31%DTS3081A460N4SS — Air Conditioner 2500 BTU 460V SS
Hammond Manufacturing · DTS3081A460N4SS
Save 31%DTS3061A460N3LG — Air Conditioner 2500 BTU 460V
Hammond Manufacturing · DTS3061A460N3LG
Save 31%DTS3061A230N3LG — Air Conditioner 2500 BTU 3R 230V LG
Hammond Manufacturing · DTS3061A230N3LG

DTS3061A115N3LG — Air Conditioner 2500BTU 3R 115V LG
Hammond Manufacturing · DTS3061A115N3LG