
Hammond 1182R60 1000 VA Toroid Transformer, 120V CT or 60V Output
Ships from and sold by A5 IT
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- Two 60V windings: 120V C.T. @ 8.3A or 60V @ 16.7A
- 2.80% voltage regulation at 1000 VA
- #12 TEW secondary leads, #16 TEW primary leads
- 3/8-16 x 3.50" mounting bolt with washers and nut
- Dual 117/234 VAC, 50/60 Hz primary (parallel for 117 V, series for 234 V)
- Class B (130 degree C) materials; 4,000 VAC RMS hi-pot primary to secondary
- UL recognized (file #E207860) and CSA certified (file #209651)
- Toroid core: low profile, lightweight, cool running, low stray flux (low EMI)
The 1182R60 is a 1000 VA toroid power transformer with two 60 V secondaries. Connected in series it is rated 120V C.T. @ 8.3A; in parallel it is rated 60V @ 16.7A. Engineers building 60 V or 120 V center-tapped supplies at the 1 kVA level can run it from 117 VAC or 234 VAC.
The drawing shows each secondary as 60V @ 8.30 A, with #16 TEW primary leads and #12 TEW secondary leads brought out 8"-9" and stripped 0.5" minimum. Regulation is 2.80% (dimension reference L). The open-center toroid is supplied with two 0.093" x 4.75" OD rubber washers, a 16GA x 4.30" OD steel mounting washer and a 3/8-16 bolt 3.50" long with lock washer and hex nut. Shipping weight is 16.5 lbs (7.48 kg).
On compliance, the 1182 family carries UL recognition to UL 5085-1 and UL 5085-2 under file #E207860 and CSA certification to C22.2 #66.1-6 and #66.2-6 under file #209651, and is self-declared as evaluated to applicable sections of IEC/EN61558-1 and IEC/EN61558-2-4. Windings use Class B (130 degree C) materials, primary-to-secondary insulation is hi-pot tested at 4,000 VAC RMS, and the part is listed as RoHS and REACH compliant.
The dual primary accepts 117 VAC (parallel connection) or 234 VAC (series connection) at 50/60 Hz, with a connection sheet included. Units are designed to run with every winding engaged, in series or parallel, or as an autotransformer. Plan the supply protection for toroidal inrush: the magnetizing current at energization is limited only by the primary's low DC resistance, so a slow-blow fuse, time-delayed breaker or soft-start is recommended.
Ideal For
- 60 V or 120 V center-tapped supplies at 1000 VA
- Equipment designed for 117 VAC or 234 VAC mains
- Equipment for both 117 VAC and 234 VAC supplies (global use)
- Designs needing low stray magnetic flux (low EMI) in a low-profile package
Overview
| Series | 1182 Series - Toroid Power Transformers, 15 VA to 1500 VA |
| Replaces | Older 182 Toroid Series |
| Description | Power transformer, toroid, 1000 VA, with 60V @ 16.7A secondary, 1182 Series |
| Part Number | 1182R60 |
| Power Rating | 1000 VA |
| Product Type | Power transformer, toroid |
| Toroid Center | Open |
| Secondary Type | Dual |
| Short Description | TOROID,1000VA, 50/60HZ, 60/60V |
| Dimension Reference | L |
Electrical
| Polarity | Additive (BLK, BRN, RED and GRY) |
| Frequency | 50/60 Hz |
| Primary Voltage | Dual 117/234 VAC |
| Primary Connection | 117 VAC: parallel connection; 234 VAC: series connection |
| Voltage Regulation | 2.80% |
| Winding Connection | All windings engaged (series or parallel connected) or connected as an autotransformer |
| Inrush Current Note | Consider a slow-blow fuse, time delayed circuit breaker or soft start circuitry on the supply line |
| Secondary (RMS) - Series | 120V C.T. @ 8.3A |
| Primary Windings (Drawing) | 2x 117V BLK-WHT, BRN-ORN |
| Secondary (RMS) - Parallel | 60V @ 16.7A |
| Secondary Windings (Drawing) | 2x 60V @ 8.30A RED-BLU, GRY-YEL |
| Hi-Pot Test, Primary - Primary | 600V, 60Hz, 1 sec |
| Secondary No-Load Voltage Test | @ 117V, 60Hz: BLK & BRN to WHT & ORN; or @ 234V, 50Hz: BLK to ORN (connect BRN & WHT) |
| Hi-Pot Test, Primary - Secondary | 4000V, 60Hz, 1 sec |
| Hi-Pot Test, Secondary - Secondary | 600V, 60Hz, 1 sec |
| Voltage Regulation (Part Page, Rounded) | 3% |
| Hi-Pot Test, Primary - Secondary (Series Spec) | 4,000 VAC RMS |
Identifiers
| UPC | 623980532004 |
| UNSPSC | 39121301 |
Leads & Wiring
| Lead Length | Minimum 8" long flexible leads |
| Connection Sheet | Included with transformer |
| Primary Lead Wire | #16 TEW |
| Secondary Lead Wire | #12 TEW |
| Primary Lead Colours | BLK-WHT (Primary #1), BRN-ORN (Primary #2) |
| Secondary Lead Colours | RED-BLU (Secondary #1), GRY-YEL (Secondary #2) |
| Lead Length & Strip (Drawing) | All leads out 8"-9" and stripped 0.5" min. |
Mounting Hardware
| Supplied Hardware 1 | Two 0.093" T x 4.75" OD rubber washers |
| Supplied Hardware 2 | One 16GA x 4.30" OD steel mounting washer |
| Supplied Hardware 3 | One 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut |
Packaging & Shipping
| Shipping Weight | 16.5 lbs (7.48 kg) |
| Weight (Drawing) | 16.29 lbs +/- 4% |
| Country Of Origin | Canada |
Construction & Finish
| Core | Toroidal |
| Toroid Benefits | Low profile, lightweight, cool running / high efficiency, low stray magnetic flux leakage (low EMI) |
| Insulation Class | Class B (130 degree C) materials |
Compliance & Certifications
| UL | UL recognized to UL 5085-1 and UL 5085-2, UL file #E207860 |
| CSA | CSA certified to C22.2 #66.1-6 and C22.2 #66.2-6, CSA file #209651 |
| IEC/EN | Self-declared evaluated to applicable sections of IEC/EN61558-1 (Second Edition 2005-09) and IEC/EN61558-2-4 |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| CE (2014 Spec Sheet) | CE compliant to IEC 61558-2-4 |
| UL (2014 Spec Sheet) | UL recognized to UL506 (XPTQ.Guide), UL file #E207860 |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What are the 1182R60 output ratings?▾
120V C.T. @ 8.3A in series or 60V @ 16.7A in parallel, at 1000 VA.
What regulation does the 1182R60 offer?▾
2.80% per the series table; the part page rounds it to 3%.
Why might the 1182R60 trip a breaker when switched on?▾
Toroidal transformers can draw high magnetizing current when first energized, limited only by the primary's low DC resistance; the overload rarely lasts longer than half a cycle. A slow-blow fuse, time-delayed circuit breaker or soft-start circuitry is recommended on the supply line.
Is it UL and CSA approved?▾
The 1182 series is UL recognized to UL 5085-1 and UL 5085-2 (file #E207860) and CSA certified to C22.2 #66.1-6 and C22.2 #66.2-6 (file #209651).
How do I wire the primary for 117 V or 234 V?▾
Connect the two 117 V primaries (BLK-WHT and BRN-ORN) in parallel for 117 VAC or in series for 234 VAC, 50/60 Hz. A connection sheet is included with the transformer.
Related Products
Save 52%1182R30 — Power transformer, toroid, 500 VA, with 30V @ 16.66A secondary, 1182 Series
Hammond Manufacturing · 1182R30
Save 52%1182S110 — Power transformer, toroid, 1000 VA, with 110V @ 9.1A secondary, 1182 Series
Hammond Manufacturing · 1182S110
Save 52%1182R117P — Power transformer, toroid, 1000 VA, with 117V @ 8.5A secondary, 1182 Series
Hammond Manufacturing · 1182R117P
Save 52%1182S12 — Power transformer, toroid, 225 VA, with 12V @ 18.76A secondary, 1182 Series
Hammond Manufacturing · 1182S12
Save 52%1182R117 — Power transformer, toroid, 1000 VA, with 117V @ 8.5A secondary, 1182 Series
Hammond Manufacturing · 1182R117
