(224) 955-1644
Hammond ManufacturingAuthorized partner store
PWS7332A115N4LG 115V 10750 BTU/H air to water heat exchanger, light gray

Hammond PWS7332A115N4LG 10750 BTU/H 115V Air-to-Water Heat Exchanger

Hammond Manufacturing|

MPN: PWS7332A115N4LG

|

UPC: 623980720470

Available on Backorder
$2,443.52

Ships from and sold by A5 IT

Available on backorder — ships as soon as stock arrives

Ground Shipping · $132.99Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 10748 BTU/h (3140 W) at +95 °F enclosure / +50 °F water
  • 441 CFM (820 m³/h) air volume
  • 115 V, 60 Hz; 453 W, 3.8 A running current
  • NEMA 3R/4 galvanized steel case in RAL7035 light gray
  • Thermostat and solenoid valve with alarm contact, +46 to +122 °F adjustable
  • 10 bar copper tube / aluminum fin core, 1/2" barb connections
  • 37.40 x 15.75 x 7.56 in; side, door or internal mounting

The PWS7332A115N4LG is the high-capacity, 115 V model of the PWS 7000 air/water heat exchanger series, listed at 10750 BTU/H, NEMA 3R/4 and light gray. It is aimed at plant engineers and panel builders cooling larger or heavily loaded enclosures with water where ambient air is hot, contaminated or subject to frequent wash-down.

Rated cooling capacity for the PWS 7332 is 10748 BTU/h (3140 W) with the enclosure at +95 °F (+35 °C) and water at +50 °F (+10 °C). It moves 441 CFM (820 m³/h) of enclosure air, needs 53 GPH (400 L/h) of coolant at rated capacity, and operates from 14.5 to 145 PSI (1 to 10 bar). Chilled water/glycol, tower water and other circulated coolants are compatible, provided the coolant is at least 10 °C colder than the inlet air.

At 115 V, 60 Hz the unit consumes 453 W and draws 3.8 A, connected at a terminal block. The integrated thermostat and solenoid valve with alarm contact control temperature automatically between +46 and +122 °F (+8 and +50 °C), factory set at +95 °F (+35 °C). The core is a rugged 10 bar copper tube / aluminum fin heat exchanger with 1/2" barb connections inside a galvanized steel case finished RAL7035 light gray.

The PWS7332A115N4LG measures 37.40 in (950 mm) high, 15.75 in (400 mm) wide and 7.56 in (192 mm) deep, and supports side, door or internal mounting with the supplied PWS 7332/7152 drilling template. Series standards are UL, cUL and CE. It ships at 60 lbs (27.22 kg) and is REACH and RoHS compliant.

Ideal For

  • High heat-load enclosures cooled from chilled water
  • Wash-down production areas with sealed panels
  • Harsh, high-ambient plant environments

Overview

SeriesPWS 7000 Series Air/Water Heat Exchanger (3000-10000 BTU/H), Type 3R, 4, 4X
ApplicationUses various water sources to cool enclosures where ambient conditions involve high temperatures, harsh conditions or frequent wash-down
DescriptionAW HX Unit 10750 BTU/H 115 V - NEMA 3R/4 - Lt. Gray
Short DescriptionAIR WATER EXCHANGER 115

Dimensions

Depth7.56 in (192 mm)
Width15.75 in (400 mm)
Height37.40 in (950 mm)

Electrical

Frequency60 Hz
ConnectionTerminal block
Running Amps3.8 A
Rated Voltage115 V
Power Consumption453 W

Accessories

Available AccessoriesRemote door switches, gasket kits, condensate bottle

Identifiers

UPC623980720470
UNSPSC40101802
Part NumberPWS7332A115N4LG

Performance

DesignLow noise, maintenance-free
Air Volume441 CFM (820 m³/h)
Heat ExchangerRugged (10 bar) copper tube / aluminum fin
Water Connection1/2" barb connection
Operating Pressure14.5 - 145 PSI (1 - 10 bar)
Compatible CoolantsChilled water/glycol, tower water and other circulated coolants
Temperature ControlIntegrated thermostat & solenoid valve with alarm contact for automatic temperature control
Adjustable Control Range+46 to +122 °F (+8 to +50 °C); factory setting +95 °F (+35 °C)
Flow Rate At Rated Capacity53 GPH (400 L/h)
Coolant Temperature RequirementCooling liquid must be at least 10 °C colder than the heat exchanger inlet air temperature
Cooling Capacity (Enclosure +95 °F / +35 °C, Water +50 °F / +10 °C)10748 BTU/h (3140 W)

Rack Mounting

Water HoseFlexible pressure-resistant (>10 bar) hose, secured with clamps
Mounting OptionsSide, door or internal mounting
Drilling TemplatePWS 7332/7152 drilling template (supplied)

Packaging & Shipping

Included ItemsCooling unit, mounting cutout, manual, technical data sheet
Shipping Weight60 lbs (27.22 kg)
Accessory Pack (Typical)Sealing strips, threaded mounting studs, mounting bolts, nuts and washers, condensate hose, door contact connector/jumper

Construction & Finish

Exterior CaseGalvanized steel construction, finish RAL7035 Light Gray

Environmental & Protection

StorageNot to be exposed to temperatures exceeding +70 °C; water circuit must be emptied with compressed air if stored or transported below freezing
Ambient Air Temperature+36 to +158 °F (+2 to +70 °C)
Enclosure Rating (Part)NEMA 3R/4
Max. Permissible Operating Pressure10 bar

Compliance & Certifications

RoHS CompliantYes
REACH CompliantYes
Series StandardsUL, cUL, and CE
Series ComplianceComplies with NEMA 3R, 4, 4X

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

How much heat can the PWS7332A115N4LG remove?▾

The PWS 7332 is rated 10748 BTU/h (3140 W) with the enclosure at +95 °F (+35 °C) and water at +50 °F (+10 °C); the part description lists 10750 BTU/H.

What are its electrical requirements?▾

115 V at 60 Hz, 453 W power consumption and 3.8 A running current, connected at a terminal block.

What are the dimensions?▾

37.40 in (950 mm) high, 15.75 in (400 mm) wide and 7.56 in (192 mm) deep.

What water flow does it require?▾

53 GPH (400 L/h) at rated capacity, at an operating pressure of 14.5 to 145 PSI (1 to 10 bar).

What ambient temperature range is it rated for?▾

The ambient air temperature rating is +36 to +158 °F (+2 to +70 °C).