(224) 955-1644
Hammond ManufacturingAuthorized partner store
PWS3302A230N4SS 12283 BTU/h 230V air/water heat exchanger with stainless steel case for enclosure cooling

Hammond PWS3302A230N4SS 12283 BTU/h Air/Water Heat Exchanger, 230V Stainless

Hammond Manufacturing|

MPN: PWS3302A230N4SS

|

UPC: 623980336534

Available on Backorder
$3,436.25

Ships from and sold by A5 IT

Available on backorder — ships as soon as stock arrives

Ground Shipping · $174.99Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • Cooling capacity 12283 BTU/h (3600 W) at +95 F enclosure / +50 F water
  • 230 V, 50/60 Hz; 59.0 W power consumption, 0.31 A running current
  • Air volume 315 CFM (535 m3/h); coolant flow 2 GPM (450 L/h) at rated capacity
  • Adjustable control range +46 to +122 F (+8 to +50 C), factory set at +95 F (+35 C)
  • 304 stainless steel case; NEMA/Type 4/4X per part description
  • Rugged (10 bar) copper tube / aluminum fin core with 1/2 in barb connection
  • Integrated thermostat and solenoid valve with alarm contact
  • Unit size 51.89 in H x 15.76 in W x 9.07 in D; side, door or internal mounting

The PWS3302A230N4SS is a full-height air/water heat exchanger from the PWS 3000 Series: the highest-capacity model of the 7000-12000 BTU/H PWS 3000 range, sharing the 51.89 in housing of the PWS 3202 while delivering 12283 BTU/h. Panel builders and OEM designers use it to cool enclosures with chilled water/glycol, tower water or other circulated coolants where ambient conditions are hot, harsh or subject to frequent wash-down.

The PWS 3302 is rated at 12283 BTU/h (3600 W) at +95 F (+35 C) enclosure and +50 F (+10 C) water; it moves 315 CFM (535 m3/h) of enclosure air on 2 GPM (450 L/h) of coolant at rated capacity. This is the 230 V version, specified for 50/60 Hz supply; it consumes 59.0 W and draws 0.31 A running current, with a terminal block power connection. An integrated thermostat and solenoid valve with alarm contact provide automatic temperature control.

The exterior case of this variant is 304 stainless steel, and the part description rates it NEMA/Type 4/4X, which suits wash-down and corrosive locations. Inside, a rugged (10 bar) copper tube / aluminum fin heat exchanger connects through a 1/2 in barb. The series ordering table gives the unit as 51.89 in (1318 mm) high, 15.76 in (400 mm) wide and 9.07 in (230 mm) deep, while the part page lists a size of 53.89 in x 16.76 in x 10.07 in (1,369 mm x 426 mm x 256 mm). Shipping weight is 70 lbs (31.75 kg). The series is rated UL, cUL and CE.

Its control range adjusts from +46 to +122 F (+8 to +50 C), factory set at +95 F (+35 C), and the unit is specified for ambient air from +36 to +158 F (+2 to +65 C). Side, door or internal mounting gives installation flexibility, and the low noise design is maintenance-free. The manual requires coolant at least 10 C colder than the inlet air.

Ideal For

  • High heat-load enclosures on a chilled water/glycol loop
  • Tower-water cooling of panels in very hot ambient air
  • Harsh-condition installations
  • Frequent wash-down areas

Quality

Leak TestingAll devices are checked for leaks before leaving the factory

Overview

ModelPWS 3302
SeriesPWS 3000 Series (7000-12000 BTU/H)
Product TypeAir/Water Heat Exchanger
Long DescriptionAir/Water Heat Exch. 3600W 230V 4/4X SS
Short DescriptionAW HX 3600W-4/4X SS

Dimensions

Depth (Series Table)9.07 in (230 mm)
Width (Series Table)15.76 in (400 mm)
Height (Series Table)51.89 in (1318 mm)
Listed Size H X W X D (Part Page)53.89 in x 16.76 in x 10.07 in (1,369 mm x 426 mm x 256 mm)

Electrical

Frequency50/60 Hz
Running Amps0.31 A
Rated Voltage230 V
Power ConnectionTerminal Block (hard wired terminal)
Power Consumption59.0 W

Accessories

Available AccessoriesRemote door switches, gasket kits, condensate bottle

Connections

Heat Exchanger Connection1/2 in barb connection

Identifiers

UPC623980336534
UNSPSC39121301
Part NumberPWS3302A230N4SS

Installation

Door ContactDoor contact switch recommended to turn the unit off when the enclosure door is opened
Mounting StyleBolt-on unit for door or side mounting on electrical panel enclosures
Mounting OptionsSide, door or internal mounting
Cooling Water HoseFlexible pressure-resistant (>10 bar) hose secured with clamps
Supply Voltage ToleranceWithin ± 10% of the ID plate value
Supply Frequency ToleranceWithin ± 3 Hz of the ID plate value
Insulation Strip Compression2 mm (approx. 0.080 in)
Coolant Temperature RequirementCooling liquid must be at least 10 C colder than the heat exchanger inlet air temperature
Maximum Permissible Operating Pressure10 bar

Cooling Performance

Air Volume315 CFM (535 m3/h)
Factory Setting+95 F (+35 C)
Operating Pressure14.5 - 145 PSI (1 - 10 bar)
Compatible CoolantsChilled water/glycol, tower water and other circulated coolants
Temperature ControlIntegrated thermostat and solenoid valve with alarm contact for automatic temperature control
Adjustable Control Range+46 to +122 F (+8 to +50 C)
Flow Rate At Rated Capacity2 GPM (450 L/h)
Cooling Capacity (Enclosure +95 F / +35 C, Water +50 F / +10 C)12283 BTU/h (3600 W)

Packaging & Shipping

Included ItemsCooling unit, mounting cutout, manual, technical data sheet
Shipping Weight70 lbs (31.75 kg)
Accessory Pack (Typical)Sealing strips, threaded mounting studs, mounting bolts, nuts and washers, condensate hose, door contact connector/jumper

Construction & Finish

DesignLow noise, maintenance-free
Exterior Case304 stainless steel
Heat Exchanger CoreRugged (10 bar) copper tube / aluminum fin

Environmental & Protection

Freezing ConditionsWater circuit must be completely emptied with compressed air before storage or transport below freezing
Ambient Air Temperature+36 to +158 F (+2 to +65 C)
Storage Temperature LimitMust not be exposed to temperatures exceeding +70 C

Compliance & Certifications

StandardsUL, cUL, and CE
RoHS CompliantYes
REACH CompliantYes
Series Enclosure RatingsNEMA 3R, 4, 4X
Enclosure Rating (Part Description)NEMA/Type 4/4X

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What is the cooling capacity of the PWS3302A230N4SS?▾

The series specification sheet rates the PWS 3302 at 12283 BTU/h (3600 W) with the enclosure at +95 F (+35 C) and the water at +50 F (+10 C).

What power supply does it need?▾

This variant is rated 230 V at 50/60 Hz, consumes 59.0 W and draws 0.31 A running current. Power connects through a terminal block. Supply voltage must be within ± 10% and frequency within ± 3 Hz of the ID plate values.

What coolants and water conditions does it accept?▾

It is compatible with chilled water/glycol, tower water and other circulated coolants. Rated capacity needs 2 GPM (450 L/h), operating pressure is 14.5 - 145 PSI (1 - 10 bar), and the coolant must be at least 10 C colder than the heat exchanger inlet air.

How is it mounted?▾

The series supports side, door or internal mounting. The manual describes bolting the unit to the enclosure with the supplied stud bolts, screws and washers, compressing the insulation strips to 2 mm (approx. 0.080 in).

Is the PWS3302A230N4SS suitable for wash-down or corrosive areas?▾

Its part description rates it NEMA/Type 4/4X with a stainless steel (304 SS) case, and the series is designed for enclosures subject to frequent wash-down.

What accessories are available?▾

The series specification sheet lists remote door switches, gasket kits and a condensate bottle as accessories. A door contact switch is recommended to turn the unit off when the enclosure door is opened.