HX94A 600V instrument potential transformer, 600:120 ratio, open Type H construction

Hammond HX94A 600V Instrument Potential Transformer, 0-20 VA

Hammond Manufacturing|

MPN: HX94A

|

UPC: 623980952840

In Stock
$89.17

Ships from and sold by A5 IT

Ground Shipping · $21.59Arrives by Monday, Oct 26
Order within 1h 53m to get it by Monday, Oct 26
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 600V nominal line voltage, 600:120 ratio for 150 Volt full scale A.C. voltmeters
  • 1.2% accuracy, 0-20 VA burden, thermal rating 100
  • Primary insulated for 4.0 KV rms test for L.V. switchgear and motor control use
  • 50/60 Hz operation
  • Open construction - "Type H"; Class 105 insulation, 55 degree C rise
  • Mounting centers 3.13 in (80 mm) x 3.13 in (80 mm); 0.22 in x 0.44 in mounting slot
  • CSA certified (209651); RoHS and REACH compliant

The HX94A is a 600V instrument potential transformer from the EX-HX-VT Series with a 600:120 ratio and the series' higher 0-20 VA burden rating. It lets a 150 Volt full scale A.C. voltmeter measure the voltage of a 600 VAC system and is intended for low-voltage switchgear and motor control panels where a heavier metering load is expected.

Electrically, the HX94A is rated for 50/60 Hz operation with 600:120 primary-to-secondary ratio, 1.2% accuracy, a 0-20 VA burden range and a thermal rating of 100. The primary is insulated for a 4.0 KV rms test, and the insulation system is Class 105 with a 55 degree C rise.

Construction is open "Type H". Overall dimensions are A 3.75 in (95 mm), B 4.00 in (102 mm) and C 3.13 in (80 mm), with mounting centers D and E both 3.13 in (80 mm) and mounting slots of 0.22 in (6 mm) (G) by 0.44 in (11 mm) (H). The spec sheet lists a ship weight of 6.6 lb; the part page lists 6.48 lbs (2.94 kg). For the same 600:120 ratio in a smaller 0-8 VA package, see the VT59A.

The HX94A is CSA certified (209651) and listed as RoHS and REACH compliant.

Ideal For

  • Voltage metering in low-voltage switchgear
  • Motor control centre voltmeter circuits
  • Driving 150 Volt full scale A.C. voltmeters on 600 VAC systems
  • Panel instrumentation on 50/60 Hz systems

Overview

SeriesEX-HX-VT Series - Potential Transformer Instrument
DescriptionPotential transformer, instrument, 600V, ratio 600:120, HX series
Part NumberHX94A
Short DescriptionVOLTAGE TRANSFORMER 100VA

Dimensions

Mounting Slot G0.22 in (6 mm)
Mounting Slot H0.44 in (11 mm)
Mounting Centers D3.13 in (80 mm)
Mounting Centers E3.13 in (80 mm)
Overall Dimension A3.75 in (95 mm)
Overall Dimension B4.00 in (102 mm)
Overall Dimension C3.13 in (80 mm)

Electrical

VA0-20
Frequency50/60 Hz
Accuracy %1.2
Intended Meter150 Volt full scale A.C. voltmeter
Thermal Rating100
Ratio Pri./Sec.600:120
Nominal Line Voltage600
Primary Insulation Test4.0 KV rms

Identifiers

UPC623980952840
UNSPSC39121301

Packaging & Shipping

Shipping Weight6.48 lbs (2.94 kg)
Ship Weight (Spec Sheet)6.6 lb

Construction & Finish

ConstructionOpen construction - "Type H"
Insulation System55 degree C rise, Class 105

Compliance & Certifications

RoHS CompliantYes
REACH CompliantYes
CSA CertificationCSA certified (209651)

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What voltage systems is the HX94A used on?▾

The HX94A has a 600V nominal line voltage and a 600:120 ratio. The series is used with 150 Volt full scale A.C. voltmeters to measure the voltage of 240, 480 or 600 VAC systems; this model is the 600V version.

What is the accuracy and burden rating of the HX94A?▾

Accuracy is 1.2%, the VA range is 0-20 and the thermal rating is 100.

Is it suitable for switchgear?▾

Yes. The primary is insulated for a 4.0 KV rms test, which the manufacturer states makes it suitable for L.V. switchgear and motor control use.

How is the HX94A mounted?▾

It is an open "Type H" construction with mounting centers of 3.13 in (80 mm) (D) and 3.13 in (80 mm) (E) and 0.22 in (6 mm) by 0.44 in (11 mm) mounting slots.

Is it CSA certified?▾

Yes, CSA certified (209651). It is also listed as RoHS and REACH compliant.