HX74A 480V instrument potential transformer, 480:120 ratio, open Type H construction

Hammond HX74A 480V Instrument Potential Transformer, 0-20 VA

Hammond Manufacturing|

MPN: HX74A

|

UPC: 623980952819

In Stock
$75.68

Ships from and sold by A5 IT

Ground Shipping · $21.59Arrives by Monday, Oct 26
Order within 51m to get it by Monday, Oct 26
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 480V nominal line voltage, 480:120 ratio for 150 Volt full scale A.C. voltmeters
  • 1.2% accuracy, 0-20 VA burden, thermal rating 100
  • Primary insulated for 4.0 KV rms test for L.V. switchgear and motor control use
  • 50/60 Hz operation
  • Nominal 480V may be exceeded by 25% for 60 Hz operation
  • Open construction - "Type H"; Class 105 insulation, 55 degree C rise
  • Mounting centers 3.13 in (80 mm) x 3.13 in (80 mm); 0.22 in x 0.44 in mounting slot
  • CSA certified (209651); RoHS and REACH compliant

The HX74A is the larger-burden 480V instrument potential transformer in the EX-HX-VT Series, stepping a 480 VAC line down at a 480:120 ratio so a 150 Volt full scale A.C. voltmeter can read the system voltage. It is aimed at panel builders and electricians fitting metering into low-voltage switchgear and motor control equipment on 480 VAC systems.

Electrically, the HX74A is rated for 50/60 Hz operation with 480:120 primary-to-secondary ratio, 1.2% accuracy, a 0-20 VA burden range and a thermal rating of 100. The primary is insulated for a 4.0 KV rms test, and the insulation system is Class 105 with a 55 degree C rise. Because its nominal line voltage is 480 volts, the series data allows that nominal to be exceeded by 25% for 60 Hz operation.

Construction is open "Type H". Overall dimensions are A 3.75 in (95 mm), B 4.00 in (102 mm) and C 3.13 in (80 mm), with mounting centers D and E both 3.13 in (80 mm) and mounting slots of 0.22 in (6 mm) (G) by 0.44 in (11 mm) (H). The spec sheet lists a ship weight of 6.6 lb; the part page lists 6.65 lbs (3.02 kg). For the same 480:120 ratio in a smaller 0-8 VA package, see the VT57A.

The HX74A is CSA certified (209651) and listed as RoHS and REACH compliant.

Ideal For

  • Voltage metering in low-voltage switchgear
  • Motor control centre voltmeter circuits
  • Driving 150 Volt full scale A.C. voltmeters on 480 VAC systems
  • Panel instrumentation on 50/60 Hz systems

Overview

SeriesEX-HX-VT Series - Potential Transformer Instrument
DescriptionPotential transformer, instrument, 480V, ratio 480:120, HX series
Part NumberHX74A
Short DescriptionVOLTAGE TRANSFORMER 100VA 480

Dimensions

Mounting Slot G0.22 in (6 mm)
Mounting Slot H0.44 in (11 mm)
Mounting Centers D3.13 in (80 mm)
Mounting Centers E3.13 in (80 mm)
Overall Dimension A3.75 in (95 mm)
Overall Dimension B4.00 in (102 mm)
Overall Dimension C3.13 in (80 mm)

Electrical

VA0-20
Frequency50/60 Hz
Accuracy %1.2
Intended Meter150 Volt full scale A.C. voltmeter
Thermal Rating100
Ratio Pri./Sec.480:120
Nominal Line Voltage480
Overvoltage AllowanceNominal line voltage of 480 volts may be exceeded by 25% for 60 Hz operation
Primary Insulation Test4.0 KV rms

Identifiers

UPC623980952819
UNSPSC39121301

Packaging & Shipping

Shipping Weight6.65 lbs (3.02 kg)
Ship Weight (Spec Sheet)6.6 lb

Construction & Finish

ConstructionOpen construction - "Type H"
Insulation System55 degree C rise, Class 105

Compliance & Certifications

RoHS CompliantYes
REACH CompliantYes
CSA CertificationCSA certified (209651)

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What voltage systems is the HX74A used on?▾

The HX74A has a 480V nominal line voltage and a 480:120 ratio. The series is used with 150 Volt full scale A.C. voltmeters to measure the voltage of 240, 480 or 600 VAC systems; this model is the 480V version.

What is the accuracy and burden rating of the HX74A?▾

Accuracy is 1.2%, the VA range is 0-20 and the thermal rating is 100.

Can the HX74A run above 480V?▾

The series data states that the nominal line voltages of 240 and 480 volts may be exceeded by 25% for 60 Hz operation, which applies to this 480V model.

Is it suitable for switchgear?▾

Yes. The primary is insulated for a 4.0 KV rms test, which the manufacturer states makes it suitable for L.V. switchgear and motor control use.

How is the HX74A mounted?▾

It is an open "Type H" construction with mounting centers of 3.13 in (80 mm) (D) and 3.13 in (80 mm) (E) and 0.22 in (6 mm) by 0.44 in (11 mm) mounting slots.

Is it CSA certified?▾

Yes, CSA certified (209651). It is also listed as RoHS and REACH compliant.