Hammond DTS3261A460N3LG 6,825 BTU/h 460V NEMA 3R/4 Side-Mount Air Conditioner
Ships from and sold by A5 IT
Available on backorder — ships as soon as stock arrives
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- 6,825 BTU/h (2,000 W) cooling capacity at +95/+95°F (+35/+35°C)
- 460 V 50/60 Hz supply, 360-506 V operating range, 2.6 A running / 16 A starting current
- IP56 and NEMA 3R, 4 compliant for outdoor enclosures
- Closed-loop cooling: enclosure air never mixes with contaminated ambient air
- Side mounting on any enclosure surface; 450 CFM internal / 450 CFM external airflow
- Thermostat adjustable +77 to +113°F (+25 to +45°C), accessible from inside the enclosure
- Built-in condensate evaporator, LED fault indication and self-diagnostics on startup
- UL, cUL and CE; gasket, mounting kit, cutout template, drain hose and clamp included
The DTS3261A460N3LG delivers 6,825 BTU/h (2,000 W) of side-mounted cooling for outdoor enclosures fed from 460 V 50/60 Hz, drawing 2.6 A running and 16 A starting. With IP56 and NEMA 3R, 4 compliance, it serves outdoor industrial control panels where engineers want larger-capacity closed-loop cooling on a 460 V supply.
Designed for side mounting on any enclosure surface, the unit uses closed loop cooling so clean enclosure air is recirculated without ever mixing with contaminated ambient air, and it keeps maximum clearance between the warm inlet and cold outlet to reduce hot spots. The exterior is NEMA 3R/4 galvanized sheet steel with a powdercoat finish in RAL7035 light gray; an ANSI 61 gray version is available by replacing LG with GY. An expansion valve prevents evaporator freeze up while minimizing heavy inrush currents.
DTS3261A460N3LG is rated 460 V 50/60 Hz with an operating range of 360-506 V, consumes 1400 W, and draws 2.6 A running and 16 A starting, wired through a terminal block. It carries a 700 g charge of R134a refrigerant, moves 450 CFM internally and 450 CFM externally (unrestricted), and uses a 150 g/m² filter mat. The thermostat, accessible from inside the enclosure, adjusts from +77 to +113°F (+25 to +45°C) with a factory setting of +95°F (+35°C). Rated ambient range is +32°F (0°C) to +131°F (+55°C), with a noise level of <73 dB(A).
Unit weight is 123 lbs (56 kg) and shipping weight is 99 lbs (44.91 kg). Gasket, mounting kit and template for the enclosure cutout and drilling are included, as are a condensate drain hose and clamp, and a built-in condensate evaporator handles condensate discharge. Self-diagnostics run on startup, faults are shown by LED, and a door contact provision allows power down when the enclosure door is opened. The series carries UL, cUL and CE approvals and complies with NEMA 3R, 4 and IP56. This part is listed as RoHS and REACH compliant.
Ideal For
- Outdoor control and automation enclosures (NEMA 3R/4, IP56)
- Weather-exposed electrical cabinets needing closed-loop cooling
- Enclosure heat loads in the 6,825 BTU/h class
- Sites with 460 V control power
Controls
| Thermostat | Accessible from inside enclosure |
| Diagnostics | Self-diagnostics on startup; fault indication via LED light |
| Door Contact | Provision for door contact allowing power down when enclosure door is opened |
Included
| Included Items | Gasket, mounting kit and template for enclosure cutout and drilling; condensate drain hose and clamp |
Overview
| Mounting | Side mounting on any enclosure surface |
| Product Type | Side-mounting outdoor enclosure air conditioner (DTS Series, 4000-7000 BTU/H, Type 3R, 4) |
| Short Description | AIR CONDIT LG |
| Manufacturer Description | Air Conditioner 3R 460V LG |
Electrical
| Line Cord | Terminal Block |
| Running Amps | 2.6 A |
| Rated Voltage | 460 V 50/60 Hz |
| Starting Current | 16 A |
| Power Consumption | 1400 W |
| Range Of Operation | 360-506 V |
| EMI/RFI Suppression | Meets CE |
Accessories
| Available Accessories | Remote Door Switches, Gasket Kits, Water Condensate Evaporator, Condensate Bottle |
Identifiers
| UPC | 623980010441 |
| UNSPSC | 40101701 |
| Part Number | DTS3261A460N3LG |
Cooling Performance
| Filter Mat | 150 g/m² |
| Noise Level | <73 dB(A) |
| Cooling Principle | Closed loop; enclosure air recirculated without mixing with ambient air |
| Refrigerant Charge | 700 g |
| Type Of Refrigerant | R134a |
| Condensate Discharge | Condensate Evaporator (built in) |
| Evaporator Protection | Expansion valve prevents evaporator freeze up while minimizing heavy inrush currents on large BTU/H units |
| Adjustable Control Range | +77..+113°F / +25..+45°C; factory setting +95°F/+35°C |
| Cooling Capacity (+95/+95°F, +35/+35°C) | 6825 BTU/h (2000 Watts) |
| Air Capacity, External Circulation (Unrestricted) | 450 CFM |
| Air Capacity, Internal Circulation (Unrestricted) | 450 CFM |
Packaging & Shipping
| Unit Weight | 123 lbs (56 kg) |
| Shipping Weight | 99 lbs (44.91 kg) |
Construction & Finish
| Finish | RAL7035 Light Gray |
| Exterior Case | Galvanized Steel |
| Alternate Finish | ANSI 61 Gray (replace LG with GY in the part number) |
| Exterior (Series) | NEMA 3R/4 exterior galvanized sheet steel with powdercoat finish |
Environmental & Protection
| NEMA Rating | Enclosures IP 56/ Nema 3R/4 |
| Series Rating | Complies with NEMA 3R, 4; IP56 |
| Max. Ambient Air Temp | +131°F (+55°C) |
| Min. Ambient Air Temp | +32°F ( 0°C) |
Compliance & Certifications
| Approvals | UL, cUL, CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What is the cooling capacity of the DTS3261A460N3LG?▾
The spec sheet rates it at 6825 BTU/h (2000 W) at +95/+95°F (+35/+35°C).
What electrical supply does the DTS3261A460N3LG require?▾
It is rated 460 V 50/60 Hz with a range of operation of 360-506 V. Power consumption is 1400 W, running current 2.6 A and starting current 16 A, connected via terminal block.
Is it suitable for outdoor enclosures?▾
Yes. The series complies with NEMA 3R, 4 and IP56, and the unit is rated for ambient temperatures from +32°F (0°C) to +131°F (+55°C).
What installation parts are included?▾
A gasket, mounting kit and template for the enclosure cutout and drilling are included, along with a condensate drain hose and clamp.
How is condensate handled?▾
The unit has a built-in condensate evaporator for condensate discharge; a drain hose and clamp are also provided. A water condensate evaporator and condensate bottle are listed as accessories.
Is a different color available?▾
This part is RAL7035 light gray. For ANSI 61 gray, the spec sheet says to replace LG with GY in the part number.
Related Products
Save 31%DTS3261A230N3LG — AC Unit 7,500 BTU/H 230 V - NEMA 3R - Lt. Gray
Hammond Manufacturing · DTS3261A230N3LG
Save 31%DTS3261A115N3LG — AC Unit 7,500 BTU/H 115 V - NEMA 3R - Lt. Gray
Hammond Manufacturing · DTS3261A115N3LG
Save 31%DTS3161A460N3LG — AC Unit 4,000 BTU/H 460 V - NEMA 3R - Lt. Gray
Hammond Manufacturing · DTS3161A460N3LG
Save 31%DTS3161A230N3LG — AC Unit 4,000 BTU/H 230 V - NEMA 3R - Lt. Gray
Hammond Manufacturing · DTS3161A230N3LG
Save 31%DTS3161A115N3LG — AC Unit 4,000 BTU/H 115 V - NEMA 3R - Lt. Gray
Hammond Manufacturing · DTS3161A115N3LG