(224) 955-1644
Hammond ManufacturingAuthorized partner store
DTS3261A115N3LG 6,825 BTU/h 115 V outdoor NEMA 3R/4 side-mount enclosure air conditioner in light gray

Hammond DTS3261A115N3LG 6,825 BTU/h 115V NEMA 3R/4 Outdoor Air Conditioner

Hammond Manufacturing|

MPN: DTS3261A115N3LG

|

UPC: 623980010380

Available on Backorder
$5,148.34

Ships from and sold by A5 IT

Available on backorder — ships as soon as stock arrives

Freight Delivery · $384.99Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 6,825 BTU/h (2,000 W) cooling capacity at +95/+95°F (+35/+35°C)
  • 115 V 60 Hz supply, 103-127 V operating range, 11.6 A running / 53 A starting current
  • IP56 and NEMA 3R, 4 compliant for outdoor enclosures
  • Closed-loop cooling: enclosure air never mixes with contaminated ambient air
  • Side mounting on any enclosure surface; 450 CFM internal / 450 CFM external airflow
  • Thermostat adjustable +77 to +113°F (+25 to +45°C), accessible from inside the enclosure
  • Built-in condensate evaporator, LED fault indication and self-diagnostics on startup
  • UL, cUL and CE; gasket, mounting kit, cutout template, drain hose and clamp included

The DTS3261A115N3LG is the larger-capacity 115 V outdoor model in this family, rated at 6,825 BTU/h (2,000 W) at +95/+95°F (+35/+35°C) and described by the manufacturer as a 7,500 BTU/H NEMA 3R light gray unit. It side-mounts on weather-exposed enclosures and moves 450 CFM on both internal and external air circuits for bigger heat loads.

Designed for side mounting on any enclosure surface, the unit uses closed loop cooling so clean enclosure air is recirculated without ever mixing with contaminated ambient air, and it keeps maximum clearance between the warm inlet and cold outlet to reduce hot spots. The exterior is NEMA 3R/4 galvanized sheet steel with a powdercoat finish in RAL7035 light gray; an ANSI 61 gray version is available by replacing LG with GY. An expansion valve prevents evaporator freeze up while minimizing heavy inrush currents.

DTS3261A115N3LG is rated 115 V 60 Hz with an operating range of 103-127 V, consumes 1680 W, and draws 11.6 A running and 53 A starting, wired through a terminal block. It carries a 700 g charge of R134a refrigerant, moves 450 CFM internally and 450 CFM externally (unrestricted), and uses a 150 g/m² filter mat. The thermostat, accessible from inside the enclosure, adjusts from +77 to +113°F (+25 to +45°C) with a factory setting of +95°F (+35°C). Rated ambient range is +32°F (0°C) to +131°F (+55°C), with a noise level of <73 dB(A).

Unit weight is 123 lbs (56 kg) and shipping weight is 141 lbs (63.96 kg). Gasket, mounting kit and template for the enclosure cutout and drilling are included, as are a condensate drain hose and clamp, and a built-in condensate evaporator handles condensate discharge. Self-diagnostics run on startup, faults are shown by LED, and a door contact provision allows power down when the enclosure door is opened. The series carries UL, cUL and CE approvals and complies with NEMA 3R, 4 and IP56. This part is listed as RoHS and REACH compliant.

Ideal For

  • Outdoor control and automation enclosures (NEMA 3R/4, IP56)
  • Weather-exposed electrical cabinets needing closed-loop cooling
  • Enclosure heat loads in the 6,825 BTU/h class
  • Sites with 115 V control power

Controls

ThermostatAccessible from inside enclosure
DiagnosticsSelf-diagnostics on startup; fault indication via LED light
Door ContactProvision for door contact allowing power down when enclosure door is opened

Included

Included ItemsGasket, mounting kit and template for enclosure cutout and drilling; condensate drain hose and clamp

Overview

MountingSide mounting on any enclosure surface
Product TypeSide-mounting outdoor enclosure air conditioner (DTS Series, 4000-7000 BTU/H, Type 3R, 4)
Short DescriptionAIR CONDIT LG
Manufacturer DescriptionAC Unit 7,500 BTU/H 115 V - NEMA 3R - Lt. Gray
Nominal Rating (Manufacturer Description)7,500 BTU/H

Electrical

Line CordTerminal Block
Running Amps11.6 A
Rated Voltage115 V 60 Hz
Starting Current53 A
Power Consumption1680 W
Range Of Operation103-127 V
EMI/RFI SuppressionMeets CE

Accessories

Available AccessoriesRemote Door Switches, Gasket Kits, Water Condensate Evaporator, Condensate Bottle

Identifiers

UPC623980010380
UNSPSC40101701
Part NumberDTS3261A115N3LG

Cooling Performance

Filter Mat150 g/m²
Noise Level<73 dB(A)
Cooling PrincipleClosed loop; enclosure air recirculated without mixing with ambient air
Refrigerant Charge700 g
Type Of RefrigerantR134a
Condensate DischargeCondensate Evaporator (built in)
Evaporator ProtectionExpansion valve prevents evaporator freeze up while minimizing heavy inrush currents on large BTU/H units
Adjustable Control Range+77..+113°F / +25..+45°C; factory setting +95°F/+35°C
Cooling Capacity (+95/+95°F, +35/+35°C)6825 BTU/h (2000 Watts)
Air Capacity, External Circulation (Unrestricted)450 CFM
Air Capacity, Internal Circulation (Unrestricted)450 CFM

Packaging & Shipping

Unit Weight123 lbs (56 kg)
Shipping Weight141 lbs (63.96 kg)

Construction & Finish

FinishRAL7035 Light Gray
Exterior CaseGalvanized Steel
Alternate FinishANSI 61 Gray (replace LG with GY in the part number)
Exterior (Series)NEMA 3R/4 exterior galvanized sheet steel with powdercoat finish

Environmental & Protection

NEMA RatingEnclosures IP 56/ Nema 3R/4
Series RatingComplies with NEMA 3R, 4; IP56
Max. Ambient Air Temp+131°F (+55°C)
Min. Ambient Air Temp+32°F ( 0°C)

Compliance & Certifications

ApprovalsUL, cUL, CE
RoHS CompliantYes
REACH CompliantYes

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What is the cooling capacity of the DTS3261A115N3LG?▾

The spec sheet rates it at 6825 BTU/h (2000 W) at +95/+95°F (+35/+35°C). The manufacturer's part description lists it as a 7,500 BTU/H unit.

What electrical supply does the DTS3261A115N3LG require?▾

It is rated 115 V 60 Hz with a range of operation of 103-127 V. Power consumption is 1680 W, running current 11.6 A and starting current 53 A, connected via terminal block.

Is it suitable for outdoor enclosures?▾

Yes. The series complies with NEMA 3R, 4 and IP56, and the unit is rated for ambient temperatures from +32°F (0°C) to +131°F (+55°C).

What installation parts are included?▾

A gasket, mounting kit and template for the enclosure cutout and drilling are included, along with a condensate drain hose and clamp.

How is condensate handled?▾

The unit has a built-in condensate evaporator for condensate discharge; a drain hose and clamp are also provided. A water condensate evaporator and condensate bottle are listed as accessories.

Is a different color available?▾

This part is RAL7035 light gray. For ANSI 61 gray, the spec sheet says to replace LG with GY in the part number.