(224) 955-1644
Hammond ManufacturingAuthorized partner store
PWS3062A230N4LG 2216 BTU/h 230V air/water heat exchanger in RAL7035 light gray for enclosure cooling

Hammond PWS3062A230N4LG 2216 BTU/h Air/Water Heat Exchanger, 230V Light Gray

Hammond Manufacturing|

MPN: PWS3062A230N4LG

|

UPC: 623980720531

Available on Backorder
$1,429.05

Ships from and sold by A5 IT

Available on backorder — ships as soon as stock arrives

Ground Shipping · $31.99Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • Cooling capacity 2216 BTU/h (650 W) at +95 F enclosure / +50 F water
  • 230 V, 50/60 Hz; 30.4 W power consumption, 0.15 A running current
  • Air volume 100 CFM (170 m3/h); coolant flow 2 GPM (450 L/h) at rated capacity
  • Adjustable control range +50 to +104 F (+10 to +50 C), factory set at +95 F (+35 C)
  • Galvanized steel case in RAL7035 Light Gray; series complies with NEMA 3R, 4, 4X
  • Rugged (10 bar) copper tube / aluminum fin core with 1/2 in barb connection
  • Integrated thermostat and solenoid valve with alarm contact
  • Unit size 24.10 in H x 10.13 in W x 5.62 in D; side, door or internal mounting

The PWS3062A230N4LG is a compact air/water heat exchanger from the PWS 3000 Series: the smallest-capacity model in the 2000-3000 BTU/H PWS 3000 range. Panel builders and OEM designers use it to cool enclosures with chilled water/glycol, tower water or other circulated coolants where ambient conditions are hot, harsh or subject to frequent wash-down.

Rated at 2216 BTU/h (650 W) with the enclosure at +95 F (+35 C) and water at +50 F (+10 C), the PWS 3062 moves 100 CFM (170 m3/h) of internal air across the coil and needs 2 GPM (450 L/h) of coolant at its rated capacity. This is the 230 V version, specified for 50/60 Hz supply; it consumes 30.4 W and draws 0.15 A running current, with a terminal block power connection. An integrated thermostat and solenoid valve with alarm contact provide automatic temperature control.

The exterior case is galvanized steel finished in RAL7035 Light Gray (LG), and the series complies with NEMA 3R, 4, 4X. Inside, a rugged (10 bar) copper tube / aluminum fin heat exchanger connects through a 1/2 in barb. The series ordering table gives the unit as 24.10 in (612 mm) high, 10.13 in (257 mm) wide and 5.62 in (143 mm) deep. Shipping weight is 20 lbs (9.07 kg). The series is rated UL, cUL and CE.

Its technical companion sheet adds a 100 % duty cycle, noise under 51 dB at 1 m, vertical installation and a 45 C alarm on an NC contact (5 A maximum input). Note that the part description for PWS3062A230N4LG shows 1000 W, while the series specification sheet rates the PWS 3062 model at 2216 BTU/h (650 W). Side, door or internal mounting gives installation flexibility, and the low noise design is maintenance-free. The manual requires coolant at least 10 C colder than the inlet air.

Ideal For

  • Cooling sealed control panels with chilled water/glycol or tower water
  • Enclosures in high-temperature ambient conditions
  • Panels in harsh environments
  • Enclosures subject to frequent wash-down

Quality

Leak TestingAll devices are checked for leaks before leaving the factory

Overview

ModelPWS 3062
SeriesPWS 3000 Series (2000-3000 BTU/H)
Product TypeAir/Water Heat Exchanger
Long DescriptionAir/Water Heat Exch. 1000W 230V LG
Short DescriptionAIR WATER EXCHANGER 1000W/230V
Rating Shown In Part Description1000 W

Dimensions

Depth (Series Table)5.62 in (143 mm)
Width (Series Table)10.13 in (257 mm)
Height (Series Table)24.10 in (612 mm)
Weight Without Packaging10 kg (22 lb)
Height X Width X Depth (Technical Sheet)613 x 257 x 143 mm (24.14 x 10.13 x 5.62 in)

Electrical

Frequency50/60 Hz
Pre-Fuse T.5 A gG
Running Amps0.15 A
Rated Voltage230 V
Power ConnectionTerminal Block (hard wired terminal)
Starting Current.16 A
Power Consumption30.4 W
Alarm Switch Setting45 C
Temperature Monitoring (Alarm)NC contact; maximum input 5 A

Accessories

Available AccessoriesRemote door switches, gasket kits, condensate bottle

Connections

Condensate Discharge1/2 in OD hose barb
Heat Exchanger Connection1/2 in barb connection
Cooling Water Connection (Technical Sheet)1/2 in push-in fitting

Identifiers

UPC623980720531
UNSPSC39121301
Part NumberPWS3062A230N4LG

Installation

Door ContactDoor contact switch recommended to turn the unit off when the enclosure door is opened
Mounting StyleBolt-on unit for door or side mounting on electrical panel enclosures
Mounting OptionsSide, door or internal mounting
Cooling Water HoseFlexible pressure-resistant (>10 bar) hose secured with clamps
Installation AttitudeVertical
Supply Voltage ToleranceWithin ± 10% of the ID plate value
Supply Frequency ToleranceWithin ± 3 Hz of the ID plate value
Insulation Strip Compression2 mm (approx. 0.080 in)
Coolant Temperature RequirementCooling liquid must be at least 10 C colder than the heat exchanger inlet air temperature
Maximum Permissible Operating Pressure10 bar

Replacement Parts

Fan Spare Part No.18611000016
Solenoid Valve (230V) Spare Part No.18785000004
(Electronic) Controller (230V) Spare Part No.18783000006
(Mechanical) Thermostat (115/230V) Spare Part No.18713000001
Temperature Sensor (Eliwell Controller Units Only) Spare Part No.18783000007

Cooling Performance

CoolantWater
Air Volume100 CFM (170 m3/h)
Duty Cycle100 %
Factory Setting+95 F (+35 C)
Operating Pressure14.5 - 145 PSI (1 - 10 bar)
Compatible CoolantsChilled water/glycol, tower water and other circulated coolants
Temperature ControlIntegrated thermostat and solenoid valve with alarm contact for automatic temperature control
Water Inlet Temperature10 C (>+1 C to +35 C) / 50 F (>+34 F to +95 F)
Adjustable Control Range+50 to +104 F (+10 to +50 C)
Thermostat Factory Setting+35 C / 95 F
Flow Rate At Rated Capacity2 GPM (450 L/h)
Range Of Adjustment (Technical Sheet)min. 10 C / 50 F - max. 40 C / 104 F
Cooling Capacity Test Point (Technical Sheet)L35 / W10 / 454 l/h
Cooling Capacity (Enclosure +95 F / +35 C, Water +50 F / +10 C)2216 BTU/h (650 W)

Packaging & Shipping

Included ItemsCooling unit, mounting cutout, manual, technical data sheet
Shipping Weight20 lbs (9.07 kg)
Accessory Pack (Typical)Sealing strips, threaded mounting studs, mounting bolts, nuts and washers, condensate hose, door contact connector/jumper

Construction & Finish

DesignLow noise, maintenance-free
FinishRAL7035 Light Gray
Exterior CaseGalvanized steel
Unit ConstructionSteel
Heat Exchanger CoreRugged (10 bar) copper tube / aluminum fin
Corrosion ProtectionGalvanized, electrostatically powder coated (200 C) - stainless steel

Environmental & Protection

Noise Level (1 M)< 51 dB
Freezing ConditionsWater circuit must be completely emptied with compressed air before storage or transport below freezing
Ambient Air Temperature+36 to +140 F (+2 to +55 C)
Storage Temperature LimitMust not be exposed to temperatures exceeding +70 C
Enclosure Internal Temperature+25 C / 77 F to +45 C / 113 F

Compliance & Certifications

StandardsUL, cUL, and CE
RoHS CompliantYes
REACH CompliantYes
Series Enclosure RatingsNEMA 3R, 4, 4X
Protective Category UL Technical Sheet)Type 12 / 3R / 4 (4X stainless steel only)

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What is the cooling capacity of the PWS3062A230N4LG?▾

The series specification sheet rates the PWS 3062 at 2216 BTU/h (650 W) with the enclosure at +95 F (+35 C) and the water at +50 F (+10 C). The part description itself shows 1000 W.

What power supply does it need?▾

This variant is rated 230 V at 50/60 Hz, consumes 30.4 W and draws 0.15 A running current. Power connects through a terminal block. Supply voltage must be within ± 10% and frequency within ± 3 Hz of the ID plate values.

What coolants and water conditions does it accept?▾

It is compatible with chilled water/glycol, tower water and other circulated coolants. Rated capacity needs 2 GPM (450 L/h), operating pressure is 14.5 - 145 PSI (1 - 10 bar), and the coolant must be at least 10 C colder than the heat exchanger inlet air.

How is it mounted?▾

The series supports side, door or internal mounting. The manual describes bolting the unit to the enclosure with the supplied stud bolts, screws and washers, compressing the insulation strips to 2 mm (approx. 0.080 in).

What finish and enclosure rating does the PWS3062A230N4LG have?▾

The exterior case is galvanized steel finished in RAL7035 Light Gray, and the series complies with NEMA 3R, 4, 4X. The series lists UL, cUL and CE.

What accessories are available?▾

The series specification sheet lists remote door switches, gasket kits and a condensate bottle as accessories. A door contact switch is recommended to turn the unit off when the enclosure door is opened.