Hammond PKS3042A115N4SS 22 W/°C 115V Mini Type 4X Stainless Heat Exchanger
Ships from and sold by A5 IT
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- 22 W/°C (12 W/°F) cooling capacity; 440W (1400 BTU) sample performance at ΔT 20°C/36°F
- Powered from 115V, 60 Hz; 82 W power consumption, 6 ft NEMA 5-15 cord
- Maintains enclosure NEMA 4X rating; IP 56; UR, cUR and CE
- Closed loop design: enclosure air never mixes with contaminated ambient air
- Unpainted 316 stainless steel cover with powder coated aluminum mounting plate
- Mounts vertically or horizontally; gasket, mounting kit and cutout/drilling template included
- 12.00 in (305 mm) H x 12.00 in (305 mm) W x 7.89 in (200 mm) D; 17 lbs (7.71 kg) shipping weight
The PKS3042A115N4SS is a compact closed loop air to air heat exchanger from the PKSMINI Series (Air to Air Heat Exchangers - Mini Type 4X), rated 22 W/°C (12 W/°F) and powered from a 115V 60 Hz supply. It is the smaller of the two mini units, and it is designed for indoor, outdoor, corrosive outdoor or washdown applications, dissipating heat from switch cabinets.
Air to air heat exchangers work when the surrounding air is cooler than the target temperature inside the enclosure, by a difference of at least 10°C/18°F. The closed loop keeps clean enclosure air recirculating without ever mixing with contaminated ambient air. At a 20°C/36°F difference between ambient and target internal temperature, the PKS3042A115N4SS delivers a sample performance of 440W (1400 BTU); actual performance depends on that ΔT. The technical sheet lists power consumption of 82 W, a maximum starting current of 0.72 A and a 6 ft (1.8 m) NEMA 5-15 line cord for the 115 VAC model, with an ambient operating range of -25°C/-13°F to +55°C/+131°F.
The unit measures 12.00 in (305 mm) high, 12.00 in (305 mm) wide and 7.89 in (200 mm) deep, with a shipping weight of 17 lbs (7.71 kg). The cover is unpainted 316 stainless steel and the mounting plate is electrostatically powder coated aluminum. It maintains the enclosure's NEMA 4X rating, is rated IP 56 and carries UR, cUR and CE marks; EMI/RFI suppression meets CE and the refrigerant is R134a.
A gasket, mounting kit and template for the cutout and drilling are included, and the unit can be mounted vertically or horizontally. Keep at least 153 mm between units and from walls, and tighten the fasteners so the seal is fully compressed (20 in-lbs). Remote door switches and gasket kits are listed as accessories.
Ideal For
- Small NEMA 4X enclosures in washdown areas
- Indoor or outdoor enclosure heat removal
- Corrosive outdoor enclosure cooling
- Closed loop cooling where ambient air is contaminated
Overview
| Series | PKSMINI Series (Air to Air Heat Exchangers - Mini Type 4X) |
| Designed For | Indoor, outdoor, corrosive outdoor or washdown applications |
| Product Type | Air to Air Heat Exchanger |
| Cooling Principle | Closed loop; clean enclosure air is recirculated without mixing with contaminated ambient air |
| Short Description | AA HX 22W/C 115V 4X SS |
| Application Condition | Surrounding air temperature lower than target internal temperature by at least 10°C/18°F |
Dimensions
| Depth | 7.89 in (200 mm) |
| Width | 12.00 in (305 mm) |
| Height | 12.00 in (305 mm) |
| Height (Technical Sheet) | 12 in (304.8 mm) |
| Nominal Size (H X W X D) | 12 in x 12 in x 7.89 in (305 mm x 305 mm x 200 mm) |
| Width X Depth (Technical Sheet) | 12 in (304.8 mm) x 7.89 in (200.4 mm) |
Electrical
| Line Cord | 6 ft (1.8 m) NEMA 5-15 |
| Power Consumption | 82 W |
| EMI/RFI Suppression | Meets CE |
| Voltage - Frequency | 115V 60 Hz |
| Starting Current (I Start Max) | 0.72 A |
| Rated Voltage (Technical Sheet, 115 VAC Model) | 115 V |
| Mains Frequency (Technical Sheet, 115 VAC Model) | 50/60 Hz |
Identifiers
| UPC | 623980274249 |
| UNSPSC | 39121301 |
| Part Number | PKS3042A115N4SS |
| Technical Sheet Model / Part Number (115 VAC | PKS 3042 / 12480112009 |
Performance
| Refrigerant | R134a |
| Performance Note | Actual cooling performance based on difference (ΔT) between ambient and target internal temperature |
| Cooling Capacity (W/°C) | 22 W/°C |
| Cooling Capacity (W/°F) | 12 W/°F |
| Ambient Air Temperature Range | -25°C / -13°F to +55°C / +131°F |
| Sample Performance At ΔT = 20°C/36°F | 440W (1400 BTU) |
| Cooling Capacity (Technical Sheet, At A20°C/+68°F) | 22 W/°C (12.2 W/°F) |
Installation
| Included | Gasket, mounting kit and template for cutout and drilling |
| Operation | Stationary operation only |
| Fastener Torque | 20 in-lbs (seal fully compressed) |
| Minimum Spacing | 153 mm between units and from the wall |
| Scope Of Delivery | Air/air heat exchanger, enclosed package (sealing profile, fastening material, electrical plug-type connectors) and special accessories if applicable |
| Mounting Orientation | Vertical or horizontal |
| Available Accessories | Remote Door Switches; Gasket Kits |
Packaging & Shipping
| Shipping Weight | 17 lbs (7.71 kg) |
| Unit Weight (Technical Sheet) | 17 lb (7.7 kg) |
Construction & Finish
| Cover | Unpainted 316 stainless steel |
| Mounting Plate | Aluminum, electrostatically powder coated |
Environmental & Protection
| Ingress Protection | IP 56 |
| Enclosure Rating Maintained | NEMA 4X |
| Protection Classification (EN 60529, Against The Enclosure) | 12 / 3R/4 & 4/4X |
Compliance & Certifications
| Approvals | UR, cUR and CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
How much heat can the PKS3042A115N4SS remove?▾
It is rated 22 W/°C (12 W/°F). As a sample, at a 20°C/36°F difference between ambient and target internal temperature it delivers 440W (1400 BTU). Actual performance depends on that temperature difference.
What power supply does the PKS3042A115N4SS need?▾
It is a 115V model; the ordering table lists 115V 60 Hz, and the technical sheet lists 115 V, 50/60 Hz, 82 W power consumption, 0.72 A maximum starting current and a 6 ft (1.8 m) NEMA 5-15 line cord.
When is an air to air heat exchanger the right choice?▾
When the surrounding air temperature is lower than the target internal temperature by at least 10°C/18°F. The closed loop recirculates clean enclosure air without mixing it with contaminated ambient air.
Will it keep my enclosure's NEMA 4X rating?▾
Yes. The PKSMINI Series maintains the enclosure's NEMA 4X rating, is rated IP 56 and carries UR, cUR and CE marks.
What comes in the box for installation?▾
A gasket, mounting kit and template for the cutout and drilling are included; the scope of delivery lists the heat exchanger plus a package with the sealing profile, fastening material and electrical plug-type connectors.
Can it be mounted horizontally?▾
Yes, it can be mounted vertically or horizontally. The unit measures 12.00 in (305 mm) H x 12.00 in (305 mm) W x 7.89 in (200 mm) D.