Hammond DTT6301B460LG 400/460V Top-Mount Air Conditioner, 5520 BTU/h
Ships from and sold by A5 IT
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- 400/460 V, 50/60 Hz supply
- 5520 BTU/h (1620 W) cooling at +95/+95F
- 962/1150 W; 3.75 / 3.6 A running, 9.8 / 11.6 A starting
- Maintains NEMA 12; IP 54; UR, cUR and CE
- Top mounting over a 19.29 x 15.50 in (490 x 394 mm) cutout
- Closed loop cooling with patented condensate management
- Shipping weight 93 lbs (42.18 kg)
The DTT6301B460LG brings 5520 BTU/h (1620 Watts) of top-mounted enclosure cooling to 400/460 V industrial installations. Part of the DTT 4000-7000 BTU/H indoor air conditioner series, it is suited to OEM machine builders and plant maintenance teams cooling NEMA 12 control cabinets fed from higher-voltage supplies, where side mounting space is not available.
Electrical ratings from the series spec sheet: 400/460 V (+/- 10%), 50/60 Hz, power consumption 962/1150 W, running current 3.75 / 3.6 A and starting current 9.8 / 11.6 A. The unit connects through a terminal block with plug, and has provision for a door contact so it can power down when the enclosure is opened. The part description identifies it as a 5300BTU 460V unit.
- Closed loop cooling: clean enclosure air is recirculated without mixing with ambient air
- Patented condensate management system and built-in condensate evaporator
- Hot gas bypass valve prevents evaporator freeze up
- R134a refrigerant; continuous circulation from high capacity fans
- Self-diagnostics on startup and LED fault indication
The thermostat is accessible from inside the enclosure, adjustable +77 to +113F (+25 to +45C) and factory set at +95F / +35C; ambient operating range is +59 to +131 F (+15 to +55 C). The DTT6301B460LG measures 17.13 in (435 mm) H x 23.43 in (595 mm) W x 19.49 in (495 mm) D and fits a 19.29 x 15.50 in (490 x 394 mm) cutout. It ships at 93 lbs (42.18 kg) with gasket, mounting kit, template, condensate drain hose and clamp, and mounts with tool-less sash fasteners. The galvanized sheet steel housing carries a RAL 7035 powder finish, and the unit maintains NEMA 12, is rated IP 54 and is UR, cUR and CE approved.
Ideal For
- Cooling enclosures on 400 V or 460 V supplies
- NEMA 12 machine control cabinets
- Top mounting where enclosure sides are occupied
- Indoor industrial electrical panels
Overview
| Series | DTT Series 4000-7000 BTU/H Indoor Air Conditioner, Type 12, Top Mounting |
| Controls | Thermostat control accessible from inside enclosure |
| Diagnostics | Self-diagnostics on startup; fault indication via LED light |
| Refrigerant | R134a |
| Door Contact | Provision for door contact allowing power down when enclosure door is opened |
| Cooling Method | Closed loop cooling; enclosure air is recirculated without mixing with ambient air |
| Hot Gas Bypass | Hot gas bypass valve prevents evaporator freeze up while minimizing heavy inrush currents on large BTU/H units |
| Air Circulation | Continuous air circulation from high capacity fans |
| Mounting Position | Top mounting (for where space does not allow side mounting on the enclosure surface) |
| Short Description | AIR CONDIT 5300BTU 460V LG |
| Condensate Evaporator | Built in |
| Condensate Management | Patented condensate management system prevents condensate from penetrating the enclosure |
Dimensions
| Size (H X W X D) | 17.13 in x 23.43 in x 19.49 in (435 mm x 595 mm x 495 mm) |
| Cutout Dimension D | 15.50 in (394 mm) |
| Cutout Dimension W | 19.29 in (490 mm) |
| Overall Dimension B (Width) | 23.43 in (595 mm) |
| Overall Dimension C (Depth) | 19.49 in (495 mm) |
| Overall Dimension A (Height) | 17.13 in (435 mm) |
Electrical
| Frequency | 50/60 Hz |
| Running Amps | 3.75 / 3.6 A |
| Starting Current | 9.8 / 11.6 A |
| Power Consumption | 962/1150 W |
| Electrical Connection | Terminal Block with Plug |
| Rated Voltage (+/- 10%) | 400/460 V |
| Cooling Capacity (+95/+95F, +35/+35C) | 5520 BTU/h (1620 Watts) |
Identifiers
| UPC | 623980336299 |
| UNSPSC | 39121301 |
Installation
| Mounting Hardware | Mounting via tool-less sash fasteners |
Packaging & Shipping
| Included | Gasket, mounting kit and template for enclosure cutout and drilling; condensate drain hose and clamp |
| Shipping Weight | 93 lbs (42.18 kg) |
| Optional Accessories | Remote Door Switches, Gasket Kits, Water Condensate Evaporator, Condensate Bottle |
Construction & Finish
| Finish (LG) | Galvanized Sheet Steel Color RAL 7035 Powder Finish |
Environmental & Protection
| Factory Setting | +95F / +35C |
| Enclosure Rating | Maintains NEMA 12 rating |
| Ingress Protection | IP 54 |
| Adjustable Control Range | +77… +113F (+25…+45C) |
| Min/Max Ambient Temperature | +59...+131 F / +15...+55 C |
Compliance & Certifications
| Approvals | UR, cUR and CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| EMI/RFI Suppression | Meets CE |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What voltage is the DTT6301B460LG rated for?▾
400/460 V (+/- 10%) at 50/60 Hz.
What is its cooling capacity?▾
5520 BTU/h (1620 Watts) at +95/+95F (+35/+35C).
What current does it draw?▾
Running current 3.75 / 3.6 A; starting current 9.8 / 11.6 A.
What cutout does it need?▾
19.29 in (490 mm) by 15.50 in (394 mm).
Can it power down when the door is opened?▾
Yes. The unit has a provision for a door contact allowing power down when the enclosure door is opened.
Related Products
Save 31%DTT6301B230LG — Air Condit 5300BTU 230V Lg
Hammond Manufacturing · DTT6301B230LG
Save 31%DTT6401B230LG — Air Condit 7100BTU 230V Lg
Hammond Manufacturing · DTT6401B230LG
Save 31%DTT6301B115LG — Air Condit 5300BTU 115V Lg
Hammond Manufacturing · DTT6301B115LG
Save 31%DTT6401B460LG — Air Condit 7100BTU 460V Lg
Hammond Manufacturing · DTT6401B460LG