Hammond DTS3141SLA115LG 5097 BTU/h 115V Indoor Slimline Air Conditioner
Ships from and sold by A5 IT
Available on backorder — ships as soon as stock arrives
Exclusive pricing and Net-30 terms. Sign in or create a free account.
Create Free Business AccountKey Features
- 5097 BTU/h (1493 W) cooling at +95/+95 °F (+35/+35 °C)
- 115 V 60 Hz supply, 103-127 V range, 917 W, 7.51 A running, 28 A starting
- Maintains NEMA 12 / IP 54 enclosure rating; UL, cUL and CE
- Narrow slimline design for side mounting on any enclosure surface
- Closed loop cooling with 350 CFM internal and 350 CFM external air
- Thermostat +77 to +113 °F (+25 to +45 °C), accessible from inside the enclosure
- Filterless, with condensate evaporator and drain hose and clamp
- Gasket, mounting kit and cutout/drilling template included
The DTS3141SLA115LG is a 115 V, 60 Hz indoor slimline air conditioner from the DTS SL Series, built for side mounting on any enclosure surface where hot spot or low capacity cooling is required. It suits panel builders, OEM engineers and facilities teams who need to pull heat out of a control cabinet running on a standard 115 V supply.
Rated cooling capacity is 5097 BTU/h (1493 W) at +95/+95 °F (+35/+35 °C). The closed loop design recirculates clean enclosure air without ever mixing it with contaminated ambient air, while high capacity fans move 350 CFM internally and 350 CFM externally (unrestricted). The unit uses R134a refrigerant with an expansion valve for improved evaporator heat transfer and less frequent compressor operation, and it is filterless with a built-in condensate evaporator.
On 115 V it has an operating range of 103-127 V, draws 917 W and 7.51 A running with a 28 A starting current, and connects by terminal block. The thermostat is adjustable from +77 to +113 °F (+25 to +45 °C), factory set to +95 °F (+35 °C), and is accessible from inside the enclosure. Ambient operating limits are +59 °F (+15 °C) to +131 °F (+55 °C), and noise is under 70 dB(A).
The case is galvanized sheet steel in RAL7035 light gray, the unit weighs 108 lbs (49 kg), and it maintains a NEMA 12 / IP 54 enclosure rating with UL, cUL and CE approvals. Self-diagnostics run on startup, faults show on an LED, and a door contact powers the unit down when the enclosure door opens. The gasket, mounting kit, cutout and drilling template, and condensate drain hose with clamp are included.
Ideal For
- Hot spot cooling on indoor control enclosures
- Low capacity cooling for NEMA 12 cabinets
- Side-mounted cooling where enclosure space is narrow
- Protecting sensitive components in switch cabinets
Cooling
| Filter Mat | Filterless |
| Refrigerant | R134a |
| Cooling Method | Closed loop - clean enclosure air is recirculated without mixing with ambient air |
| Air Circulation | Continuous, from high capacity fans |
| Expansion Valve | Improves evaporator heat transfer with less frequent compressor operation |
| Refrigerant Charge | 700 g or 900 g depending on voltage (series data) |
| Condensate Discharge | Condensate evaporator |
| Condenser/Evaporator | Built in |
| Air Capacity (Unrestricted) | Internal circulation 350 CFM; external circulation 350 CFM |
| Cooling Capacity (+95/+95 F, +35/+35 C) | 5097 BTU/h (1493 W) |
Controls
| Thermostat | Accessible from inside enclosure |
| Diagnostics | Self-diagnostics on startup; fault indication via LED light |
| Door Contact | Powers the unit down when the enclosure door is opened |
| Factory Setting | +95 °F (+35 °C) |
| Adjustable Control Range | +77 to +113 °F / +25 to +45 °C |
Overview
| Series | DTS SL Series - 3000-5000 BTU/H Indoor Slimline Air Conditioner, Type 12, Side Mounting |
| Part Number | DTS3141SLA115LG |
| Long Description | AC Unit 3500-5000 BTU/H 115 V - NEMA 12 - Lt. Gray |
| Drawing Tolerance | ISO 2768-m |
| Reference Drawing | DTS 31x5 W/ Rain Shield, drawing 30240-600 01 |
| Short Description | AIR CONDIT 3500BTU 115V LG |
| Optional Accessories | Remote door switches, filter kits, gasket kits, water condensate evaporator, condensate bottle |
Dimensions
| Unit Weight | 108 lbs (49 kg) |
| Drawing Units | mm [inch] |
| Drawing Dimension | 838.20 mm (33.00 in) |
| Drawing Dimension (Width) | 366.16 mm (14.42 in) |
| Drawing Dimensions (Other) | 312 mm (12.28 in); 310.90 mm (12.24 in); 302.21 mm (11.90 in); 279.40 mm (11.00 in); 245.66 mm (9.67 in); 243.62 mm (9.59 in) |
| Drawing Largest Overall Dimension | 917.03 mm (36.10 in) |
Electrical
| Line Cord | Terminal Block |
| Running Amps | 7.51 A |
| Rated Voltage | 115 V 60 Hz |
| Starting Current | 28 A |
| Power Consumption | 917 W |
| Range Of Operation | 103-127 V |
| EMI/RFI Suppression | Meets CE |
Identifiers
| UPC | 623980568157 |
| UNSPSC | 40101701 |
Installation
| Mounting | Side mounting on any enclosure surface |
Packaging & Shipping
| Included | Gasket, mounting kit and template for cutout and drilling; condensate drain hose and clamp |
| Shipping Weight | 113 lbs (51.26 kg) |
Construction & Finish
| Finish | RAL7035 light gray (LG) |
| Exterior Case | Galvanized sheet steel |
| Alternate Finish | ANSI 61 Gray - replace LG with GY in the part number |
| Drawing Material | 18GA galvanized; CRS powder coated |
Environmental & Protection
| IP Rating | IP 54 |
| Noise Level | <70 dB(A) |
| Max Ambient Air Temp | +131 °F (+55 °C) |
| Min Ambient Air Temp | +59 °F (+15 °C) |
Compliance & Certifications
| Approvals | UL, cUL and CE |
| NEMA Rating | Maintains NEMA 12 rating (Enclosures IP 54/Nema 12) |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Purchasing this for your business?
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Frequently Asked Questions
What voltage does the DTS3141SLA115LG run on?▾
It is rated 115 V 60 Hz with an operating range of 103-127 V, and it connects by terminal block.
How much cooling does it provide?▾
5097 BTU/h (1493 W) at +95/+95 °F (+35/+35 °C).
What current should I plan for?▾
Running current is 7.51 A, starting current is 28 A, and power consumption is 917 W.
Does it keep my enclosure NEMA 12?▾
Yes. The unit maintains a NEMA 12 rating and is IP 54, with UL, cUL and CE approvals.
Does it need a filter?▾
No. It is filterless and discharges condensate through a condensate evaporator; a condensate drain hose and clamp are included. Filter kits are listed as an optional accessory.
What ambient temperatures can it handle?▾
Between +59 °F (+15 °C) and +131 °F (+55 °C).