(224) 955-1644
Hammond ManufacturingAuthorized partner store
DTS3041A460LG 460 V indoor NEMA 12 enclosure air conditioner with light gray case

Hammond DTS3041A460LG 2610 BTU/h 460V NEMA 12 Indoor Air Conditioner

Hammond Manufacturing|

MPN: DTS3041A460LG

|

UPC: 623980468914

Available on Backorder

Call for Price

Ships from and sold by A5 IT

Call for pricing

This part is quoted to order. Call for current pricing, lead time and volume breaks on the Hammond Manufacturing DTS3041A460LG.

224-955-1644
Ground Shipping · $132.99Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty

Key Features

  • 460 V 50/60 Hz, 360-506 V range, 789 W, 0.76 A running current
  • 2610 BTU/h (765 W) at +95/+95F (+35/+35C)
  • Maintains NEMA 12 enclosure rating; IP 54; UR, cUR and CE
  • 22.96 x 10.05 x 10.74 in (583 x 255 x 273 mm) overall
  • Terminal block connection; phase-sensitive three phase supply
  • Self-diagnostics on startup and LED fault indication
  • Gasket, mounting kit and cutout/drilling template included

The DTS3041A460LG is the 460 V member of the DTS Series indoor air conditioners, sized for side mounting on any enclosure surface where hot spot cooling or low capacity cooling is required. Rated 460 V 50/60 Hz, it lets OEM machine builders and plant electricians cool NEMA 12 cabinets directly from a 460 V supply.

The closed loop design recirculates clean enclosure air without letting it mix with contaminated ambient air. Cooling capacity on the data sheet is 2610 BTU/h (765 Watts) at +95/+95F (+35/+35C); the part description refers to it as a 2500 BTU unit. It uses R134a (400 g charge) with an expansion valve for improved evaporator heat transfer and less frequent compressor operation, plus 191 CFM internal and 88 CFM external circulation.

Electrical ratings are 360-506 V range of operation, 789 W, 0.76 A running and 10.4 A starting current, with a terminal block connection. The manual notes that on three phase (400V/460V) units the supply connections are phase sensitive, so connections must be correct for the unit to operate properly. The drilling template includes an additional cutout area marked for 400/460V units only.

At 22.96 in H x 10.05 in W x 10.74 in D (583 x 255 x 273 mm), the DTS3041A460LG is taller than the 115 V and 230 V versions; the part page lists a size of 26 x 12 x 14 in (660 x 305 x 356 mm) and a shipping weight of 64 lbs (29.03 kg). The galvanized sheet metal case is RAL7035 light gray. It maintains the enclosure's NEMA 12 rating, is rated IP 54 and carries UR, cUR and CE.

Self-diagnostics on startup, LED fault indication, a door contact for power down, filterless operation and a 1/2" NPT condensate port are standard; the gasket, mounting kit and template are included.

Ideal For

  • 460 V indoor NEMA 12 control cabinets
  • Hot spot cooling for industrial machinery panels
  • Low capacity side-mounted enclosure cooling

Overview

MountingSide mounting
Part NumberDTS3041A460LG
Cooling TypeClosed loop
Product Type2000-3000 BTU/H Indoor Air Conditioner, DTS Series
Long DescriptionAir Conditioner 2500 BTU 460V LG
Short DescriptionAIR CONDIT 2500BTU 460V LG

Dimensions

Unit Weight61.7 lbs (28 kg)
Overall Depth10.74 in (273 mm)
Overall Width10.05 in (255 mm)
Overall Height22.96 in (583 mm)
Drawing Overall Height583.35 mm (22.97 in)
Nominal Size (H X W X D)26 in x 12 in x 14 in (660 mm x 305 mm x 356 mm)

Electrical

Line CordTerminal Block
Phase NoteOn three phase connection (400V/460V) units the power supply connections are phase sensitive
Door ContactDoor contact for power down when enclosure door is opened
Running Amps0.76 A
Rated Voltage460 V 50/60 Hz
Starting Current10.4 A
Power Consumption789 W
Range Of Operation360-506 V
EMI/RFI SuppressionMeets CE

Accessories

Available AccessoriesRemote Door Switches, Filter Kits, Gasket Kits, Water Condensate Evaporator, Condensate Bottle

Identifiers

UPC623980468914
UNSPSC40101701

Performance

ThermostatThermostat control accessible from inside enclosure
DiagnosticsSelf-diagnostics on startup; fault indication via LED light
Noise Level<64 dB (A)
RefrigerantR134a
Expansion ValveIncreases efficiency with improved evaporator heat transfer and less frequent compressor operation
Factory Setting+95°F / +35C
Refrigerant Charge400 g
Adjustable Control Range+50F..+104F / +10C..+40C
Cooling Capacity (+95/+95F, +35/+35C)2610 BTU/h (765 Watts)
Air Capacity, External Circulation (Unrestricted)88 CFM
Air Capacity, Internal Circulation (Unrestricted)191 CFM

Installation

Template NotePatterned cutout area on the drilling template is for 400/460V units only
Drilling TemplateDrilling template DTS 30xx, part number 18380000007

Packaging & Shipping

IncludedGasket, mounting kit and template for cutout and drilling
Shipping Weight64 lbs (29.03 kg)
Scope Of DeliveryDTS cooling unit, cooling unit quick guide, accessory kit (seal, fastening material, electrical plug connector, etc.)

Construction & Finish

FinishRAL7035 light gray (LG)
Colour OptionFor ANSI 61 Gray replace LG with GY
Exterior CaseGalvanized sheet metal

Environmental & Protection

Filter MatFilterless (aluminum, fleece and fluted filters possible with an additional adapter)
NEMA / IP RatingEnclosures IP 54 / NEMA 12; maintains enclosure's NEMA 12 rating
Max Ambient Air Temp+114F (+45°C)
Min Ambient Air Temp+46°F (+8°C)
Condensation DischargeCondensate drain; direct discharge via 1/2" NPT threaded port

Compliance & Certifications

StandardsUR, cUR and CE
RoHS CompliantYes
REACH CompliantYes
Material DeclarationRoHS-compliant and free from silicone connections, PCT, asbestos, formaldehyde, cadmium and moisture-impairing substances

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What supply does the DTS3041A460LG need?▾

460 V 50/60 Hz, with a range of operation of 360-506 V. It consumes 789 W and draws 0.76 A running, 10.4 A starting.

Is the 460 V version the same size as the 115 V and 230 V models?▾

No. The DTS3041A460LG is 22.96 in (583 mm) high versus 20.15 in for the lower-voltage models; width 10.05 in and depth 10.74 in are the same.

Does wiring phase matter?▾

Yes. The manual states that on three phase (400V/460V) units the power supply connections are phase sensitive and must be correct or the unit will not operate properly.

Is it suitable for outdoor enclosures?▾

It is an indoor air conditioner that maintains the enclosure's NEMA 12 rating and is rated IP 54.

What is the shipping weight?▾

64 lbs (29.03 kg). The data sheet lists a unit weight of 61.7 lbs (28 kg).