CSBL400 400 A splitter block with Cu-Al main lug and six branch lugs

Hammond CSBL400 400A Splitter Block, 600V Cu-Al Main & Branch Lugs

Hammond Manufacturing|

MPN: CSBL400

|

UPC: 623980263847

In Stock
$42.39

Ships from and sold by A5 IT

Ground Shipping · $16.89Arrives by Monday, Oct 26
Order within 1h 2m to get it by Monday, Oct 26
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 400 A main lug: 600MCM-4, or (2x) 250 MCM-1/0
  • Six branch lugs: 6/200 ampacity, 6 x (3/0-14) wire capacity
  • Copper or aluminum conductors on all lugs
  • Cu-Al monopiece connectors secured to insulators
  • Rated 600 V; 75 °C conductor ampacity permitted
  • For Hammond standard splitter troughs and boxes
  • REACH and RoHS compliant

The CSBL400 is a 400 A splitter block from the CSBL Series, used in Hammond standard splitter troughs and boxes. It is intended for electricians working on 400 A class distribution who need a block to fit, replace or add to a splitter enclosure.

The main lug is rated 400 A. Its max./min. wire capacity is 600MCM - 4, or alternatively two conductors of 250 MCM - 1/0. Branch ampacity is listed as 6/200, and the branch lugs take 6 x (3/0-14), so six branch conductors from 3/0 to 14 can be connected.

The block is made from Cu-Al monopiece connectors secured to insulators and includes a main lug and branch lugs. Main and branch lugs can use either copper or aluminum conductors. All CSBL blocks are rated 600 V, with 75 °C conductor ampacity permitted.

  • Main lug: 400 A, 600MCM - 4 or (2x) 250 MCM - 1/0
  • Branch lugs: 6/200 ampacity, 6 x (3/0-14) wire capacity
  • Voltage: 600 V, copper or aluminum conductors
  • Connectors: Cu-Al monopiece, secured to insulators
  • Packaging: bag, 0.5 lbs (0.23 kg)

The CSBL400 is REACH and RoHS compliant. It ships in a bag at 0.5 lbs (0.23 kg), UPC 623980263847.

Ideal For

  • 400 A splitter block for Hammond standard splitter boxes and troughs
  • Paralleled main conductors split to six branch runs
  • Replacement block for 400 A splitter installations

Overview

SeriesCSBL Series – Splitter Blocks
DescriptionSplitter Blocks 400 A
Part NumberCSBL400

Electrical

Voltage Rating600 V
Main Lug Ampacity400 A
Conductor MaterialMain and branch lugs accept copper or aluminum conductors
Branch Lugs Ampacity6/200
Conductor Temperature75 °C conductor ampacity permitted
Main Lug Max./Min. Wire Capacity600MCM - 4 or (2x) 250 MCM - 1/0
Branch Lugs Max./Min. Wire Capacity6 x (3/0-14)

Identifiers

UPC623980263847
UNSPSC39121410

Packaging & Shipping

Packaging TypeBag
Shipping Weight0.5 lbs (0.23 kg)

Construction & Finish

ConnectorsCu-Al monopiece connectors secured to insulators
Included LugsOne main lug and branch lugs per block

Compliance & Certifications

RoHS CompliantYes
REACH CompliantYes

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

Can the CSBL400 main lug take two conductors?▾

Yes. The main lug wire capacity is 600MCM - 4, or (2x) 250 MCM - 1/0.

What size branch conductors does it accept?▾

Branch capacity is 6 x (3/0-14): six branch lugs for 3/0 to 14 wire, with branch ampacity listed as 6/200.

Is it suitable for aluminum wire?▾

Yes. The main and branch lugs can use either copper or aluminum conductors.

What is the voltage rating?▾

All CSBL Series blocks are rated 600 V.