1182N240 750 VA toroid power transformer with dual 117/234 VAC primary and single 240V secondary, flexible colour-coded leads

Hammond 1182N240 750 VA Toroid Power Transformer, 240V Single Secondary

Hammond Manufacturing|

MPN: 1182N240

|

UPC: 623980531977

Available on Backorder
$126.03

Ships from and sold by A5 IT

Available on backorder — ships as soon as stock arrives

Ground Shipping · $25.10Ships as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Business Pricing Available

Exclusive pricing and Net-30 terms. Sign in or create a free account.

Create Free Business Account

Key Features

  • 750 VA rating with a single 240V @ 3.13A secondary
  • Dual 117/234 VAC primary for 50/60 Hz operation on either supply voltage
  • 3.60% voltage regulation per the series ordering table
  • Toroidal core: low profile, lightweight, cool running, low stray flux (low EMI)
  • Mounting kit: rubber pads, 4.30 in OD steel washer and 3/8-16 bolt with nut
  • #16 TEW primary and #16 TEW secondary leads, 8-9 in long, stripped 0.5 in min
  • UL recognized (E207860) and CSA certified (209651); 4,000 VAC hi-pot, Class B materials

The 1182N240 is a 750 VA toroidal power transformer in the 1182 Series with a dual 117/234 VAC, 50/60 Hz primary and a single 240V secondary rated 3.13A. It is aimed at OEM engineers, panel builders and service technicians who need a 240V output from either 117 VAC or 234 VAC mains, using one part for both supply voltages.

Unlike the dual-secondary models in the series, the 1182N240 has one secondary winding, brought out on the red and blue leads (1x 240V @ 3.13A RED-BLU). The primary is split into two 117 V windings (BLK-WHT and BRN-ORN) that are connected in parallel for 117 VAC or in series for 234 VAC. Voltage regulation is listed at 3.60%.

The toroidal core shape gives a low profile, light weight, cool running and high efficiency, with low stray magnetic flux leakage for low EMI. This unit has an open toroid centre (dimension reference K), is manufactured using Class B (130 °C) materials and weighs 12.87 lb +/- 4% according to its drawing, with a listed shipping weight of 13 lbs (5.90 kg).

For installation, the 1182N240 ships with two 0.093 in thick x 4.75 in OD rubber washers, one 16 ga x 4.30 in OD steel mounting washer and one 3/8-16 bolt, 3.50 in long, with lock washer and 3/8-16 hex nut. Primary leads are #16 TEW and secondary leads are #16 TEW, all brought out 8 to 9 in and stripped 0.5 in minimum. Because toroids can draw high magnetizing current when first energized, the manufacturer recommends a slow-blow fuse, time-delayed circuit breaker or other soft-start circuitry on the supply line.

The 1182 Series is UL recognized to UL 5085-1 and UL 5085-2 (file E207860), CSA certified to C22.2 #66.1-6 and #66.2-6 (file 209651), and hi-pot tested at 4,000 VAC RMS between primary and secondary. This part is RoHS and REACH compliant and is made in Canada.

Ideal For

  • 240V supply from 117 VAC or 234 VAC mains
  • Equipment built for global use on 50/60 Hz supplies
  • Low-EMI designs that benefit from low stray magnetic flux
  • Bolt-down mounting with the included insulating pads and hardware

Mounting

Mounting BoltOne 3/8-16 bolt, 3.50" long, with lock washer and 3/8-16 hex nut
Steel Mounting WasherOne, 16 GA x 4.30" OD
Rubber Insulating WashersTwo, 0.093" T x 4.75" OD

Overview

Series1182
ReplacesOlder 182 Toroid Series
DescriptionPower transformer, toroid, 750 VA, with 240V @ 3.13A secondary, 1182 Series
Product TypeToroid power transformer
Short DescriptionTOROID, 750VA,50/60HZ,240

Electrical

PrimaryDual 117/234 VAC (2x 117V windings: BLK-WHT, BRN-ORN)
PolarityAdditive (BLK, BRN and RED)
Frequency50/60 Hz
Inrush NoteUse a slow-blow fuse, time-delayed circuit breaker or other soft-start circuitry on the supply line
Power Rating750 VA
Secondary TypeSingle
Connection NoteAll windings to be engaged (series or parallel connected) or connected as an autotransformer; connection sheet included
Secondary (RMS)240V @ 3.13A
% Voltage Regulation3.60%
Primary Wiring, 117 VACParallel connection (BLK & BRN to WHT & ORN)
Primary Wiring, 234 VACSeries connection (BLK to ORN, connect BRN & WHT)
Secondary Winding (Drawing)1x 240V @ 3.13A RED-BLU
% Voltage Regulation (Part Page)4

Identifiers

UPC623980531977
UNSPSC39121301
Part Number1182N240
Country Of OriginCanada
Label Code (Drawing)1A0750A000A000240

Packaging & Shipping

Shipping Weight13 lbs (5.90 kg)
Weight (Drawing)12.87Lbs +/- 4%

Construction & Finish

Lead Length8"-9" (minimum 8" flexible leads)
Core BenefitsLow profile, lightweight, cool running / high efficiency, low stray magnetic flux leakage (low EMI)
Primary Leads#16 TEW
Toroid CenterOpen
Secondary Leads#16 TEW
Lead Strip Length0.5" min.
Dimension ReferenceK
Insulation MaterialsClass B (130 °C)

Environmental & Protection

Hi-Pot, Primary-Primary600V, 60Hz, 1 sec
Hi-Pot, Primary-Secondary4,000 VAC RMS (4000V, 60Hz, 1 sec)

Compliance & Certifications

ULRecognized to UL 5085-1 and UL 5085-2, file #E207860
CSACertified to C22.2 #66.1-6 and C22.2 #66.2-6, file #209651
IEC/ENSelf-declared, evaluated to applicable sections of IEC/EN61558-1 (Second Edition 2005-09) and IEC/EN61558-2-4
RoHS CompliantYes
REACH CompliantYes

Purchasing this for your business?

Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.

Wholesale pricing below retail
Net-30 terms for qualified businesses
Volume discount tiers
Dedicated account representative
Saved payment methods & PO support
Priority order processing
Create Free Business Account

Frequently Asked Questions

What output does the 1182N240 provide?▾

A single 240V secondary rated 3.13A (750 VA), available from either a 117 VAC or 234 VAC supply at 50/60 Hz.

How do I wire the 1182N240 primary for 117 V or 234 V?▾

For 117 VAC connect the two primary windings in parallel (BLK & BRN to WHT & ORN). For 234 VAC connect them in series by joining BRN and WHT and applying the supply across BLK and ORN.

What mounting hardware comes with the 1182N240?▾

Two 0.093" thick x 4.75" OD rubber washers, one 16 gauge x 4.30" OD steel mounting washer, and one 3/8-16 bolt 3.50" long with a lock washer and hex nut.

Why might the breaker trip when the transformer is switched on?▾

Toroidal transformers can draw a high magnetizing current at switch-on, limited only by the primary's low DC resistance, usually for no more than half a cycle. A slow-blow fuse, time-delayed breaker or soft-start circuit is recommended.

What certifications does the 1182N240 carry?▾

The 1182 Series is UL recognized to UL 5085-1 and UL 5085-2 (file E207860) and CSA certified to C22.2 #66.1-6 and #66.2-6 (file 209651). The part is also listed as RoHS and REACH compliant.

How much does the 1182N240 weigh?▾

The drawing gives 12.87 lb +/- 4%; the listed shipping weight is 13 lbs (5.90 kg).