(224) 955-1644
Hammond ManufacturingAuthorized partner store

Type 4, 4X Single Door Selection Guide

Space Occupied by Disconnect

Disconnects will occupy space on panel shown by dimensions "K", "L" and "M".

Wiring space "P" is available when disconnect is installed in the enclosure.

*The disconnect information and space occupied tables based on data supplied by disconnect manufacturer’s bulletins. Hammond Manufacturing not responsible for dimensional accuracy.

ABB Controls Disconnect Switches (Flange Mounted Operators)

¹ J type fuse clips are standard. If 600 V Type “T” fuse clips are desired order T type fuse adaptor kit. ² 200 A available by using non-fusible 200A switch and a trailing fuse block. (consult ABB)

ABB Controls Circuit Breaker (Flange Mounted Operators)

Charts reference Space Occupied by Disconnect Drawing.

1 Series B 2 "M" dimension does not allow for auxiliary switches.

Allen Bradley 1494U Circuit Breakers

1 "M" dimension does not allow for auxiliary switches. Charts reference Space Occupied by Disconnect Drawing.

Cutler Hammer Cutler Hammer C361 Disconnect Switches

Part numbers for Complete Operator Mechanisms include flange mounted handle, flexible shaft and circuit breaker mechanism. The last digit of the part number denotes the shaft length (F1S03=3' length).

Space Occupied By Disconnect 1. Flex-Shaft™ System permits circuit breaker locations separate from flange mounted handle mechanism. 2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref “P”) needed for line side conductors. 3. Select shaft length based on location of circuit breaker in the enclosure. Maintain a 4" minimum bending radius for the Flex-Shaft™. 4. Space occupied by circuit breaker is calculated by:

Charts reference Space Occupied by Disconnect Drawing.

General Electric

General Electric Type STDA Disconnect Switches

Charts reference Space Occupied by Disconnect Drawing.

Space Occupied By Disconnect 1. I-T-E Max-Flex™ System permits circuit breaker locations separate from flange mounted handle mechanism. 2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref “P”) needed for line side conductors. 3. See Siemens I-T-E instructions for disconnect location limitations when using 36" or 48" Max-Flex™ cables. 4. Space occupied by circuit breaker is calculated by:

Square D Class 9422 Variable Depth Operators (Circuit Breakers)

Space Occupied By Disconnect Switch 1. Square D Cable System permits circuit breaker locations separate from flange mounted handle mechanism. 2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") needed for line side conductors. 3. Select cable mechanism length based on disconnect location in enclosure. See Square D instructions for minimum cable bend radius. 4. Space occupied by circuit breaker is calculated by:

Charts reference Space Occupied by Disconnect Drawing.

  • ■F,J,K frame Flex-Shafts™ available in 3' to 10' lengths.
  • ■L,N,R frame Flex-Shafts™ available in 4' to 6' lengths.
  • ■Overall (Height "X" and Width "Y")
  • ■Minimum wire bend space (manufacturer specified)
  • ■Location "M" from right to left.
  • ■GE Spectra-Flex™ Operating Cables permit circuit breaker locations separate from flange mounted handle mechanism.
  • ■See National Electrical Code 2005 article 430-10(b) for wiring space (Ref “P”) needed for line side conductors.
  • ■Select shaft length based on location of circuit breaker in the enclosure. Maintain a 3" minimum bending radius for the Flex-Shaft™.
  • ■Space occupied by circuit breaker is calculated by: Overall (Height "X" and Width "Y") Minimum wire bend space (manufacturer specified) Location "M" from right to left
  • ■Overall (Height "X" and Width "Y")
  • ■Minimum wire bend space (manufacturer specified)
  • ■Location "M" from right to left
  • ■Overall (Height "X" and Width "Y")
  • ■Minimum wire bend space (manufacturer specified)
  • ■Location "M" from right to left.
  • ■Charts reference Space Occupied by Disconnect Drawing.
  • ■Overall (Height "X" and Width "Y")
  • ■Minimum wire bend space (manufacturer specified)
col1col2col3col4
Hammond SeriesHammond Series1447SEN4DCS all versions
ABB ControlsDisconnect SwitchFlange operated switch (fusible or non-fusible)Flange operated switch (fusible or non-fusible)
ABB ControlsDisconnect SwitchShaft: 8-12” dp enclosures, use DSFHS-12; 16” dp enclosures, use DSFHS-17Shaft: 8-12” dp enclosures, use DSFHS-12; 16” dp enclosures, use DSFHS-17
ABB ControlsDisconnect SwitchHandle: DSFHN-HS4Handle: n/a
ABB ControlsDisconnect SwitchDoor Hardware: n/aDoor Hardware: n/a
ABB ControlsCircuit BreakerCircuit breaker: ABBCircuit breaker: ABB
ABB ControlsCircuit BreakerOperating Mechanism: see ABB chartOperating Mechanism: see ABB chart
ABB ControlsCircuit BreakerShaft: 8-12” dp enclosures, use K7FHD-S12; 16” dp enclosures, use K7FHD-S17Shaft: 8-12” dp enclosures, use K7FHD-S12; 16” dp enclosures, use K7FHD-S17
ABB ControlsCircuit BreakerHandle: K7FHD-HS4Handle: n/a
ABB ControlsCircuit BreakerDoor Hardware: n/aDoor Hardware: n/a
Allen Bradley1494U Flange Disconnect SwitchDisconnect switch and operating mechanism: Bulletin 1494UDisconnect switch and operating mechanism: Bulletin 1494U
Allen Bradley1494U Flange Disconnect SwitchHandle: Bulletin 1494U-W1Handle: n/a
Allen Bradley1494U Flange Disconnect SwitchConnecting rod: 8-10” dp enclosures, use 1494U-RA1; 12-16” dp enclosures, use 1494U-RA2Connecting rod: 8-10” dp enclosures, use 1494U-RA1; 12-16” dp enclosures, use 1494U-RA2
Allen Bradley1494U Flange Disconnect Switch(except for Hammond part # 1447S46L12, use 1494U-RB2 (2))(except for Hammond part # 1447S46L12, use 1494U-RB2 (2))
Allen Bradley1494U Flange Disconnect SwitchTrailer fuse block kit (if required): Bulletin 1494UTrailer fuse block kit (if required): Bulletin 1494U
Allen Bradley1494U Flange Disconnect SwitchFuse kit (if required)Fuse kit (if required)
Allen Bradley1494U Flange Disconnect SwitchLine and load connectors (if required)Line and load connectors (if required)
Allen Bradley1494U Flange Disconnect SwitchDoor Hardware: n/aDoor Hardware: n/a
Allen Bradley1494U Flange Circuit BreakerCircuit breaker: C-H WestinghouseCircuit breaker: C-H Westinghouse
Allen Bradley1494U Flange Circuit BreakerOperating mechanism: Bulletin 1494UOperating mechanism: Bulletin 1494U
Allen Bradley1494U Flange Circuit BreakerHandle: Bulletin 1494U-W11Handle: n/a
Allen Bradley1494U Flange Circuit BreakerConnecting rod: 8-10” dp enclosures, use 1494U-RA1; 12-16” dp enclosures, use 1494U-RA2Connecting rod: 8-10” dp enclosures, use 1494U-RA1; 12-16” dp enclosures, use 1494U-RA2
Allen Bradley1494U Flange Circuit BreakerDoor Hardware: n/aDoor Hardware: n/a
Cutler HammerType C361 Disconnect SwitchDisconnect switch and operating mechanismDisconnect switch and operating mechanism
Cutler HammerType C361 Disconnect SwitchHandle: C361-H2 or H4Handle: n/a
Cutler HammerType C361 Disconnect SwitchDoor Hardware: n/aDoor Hardware: n/a
Cutler HammerType C371 Circuit BreakerCircuit breaker: C-H WestinghouseCircuit breaker: C-H Westinghouse
Cutler HammerType C371 Circuit BreakerOperating mechanismOperating mechanism
Cutler HammerType C371 Circuit BreakerHandle: 150 amp, use C371H2 or H4; 250-600 amp, use C371H6 or H8Handle: n/a
Cutler HammerType C371 Circuit BreakerDoor Hardware: n/aDoor Hardware: n/a
Cutler HammerC-H Westinghouse Circuit Breaker w/FlexShaftCircuit breakerCircuit breaker
Cutler HammerC-H Westinghouse Circuit Breaker w/FlexShaftComplete Flex-Shaft handle mechanismComplete Flex-Shaft handle mechanism
Cutler HammerC-H Westinghouse Circuit Breaker w/FlexShaftDoor Hardware: n/aDoor Hardware: n/a
General ElectricType STDA Flange Disconnect SwitchDisconnect switch Type QMR or QMWDisconnect switch Type QMR or QMW
General ElectricType STDA Flange Disconnect SwitchHandle: STDA1XHandle: n/a
General ElectricType STDA Flange Disconnect SwitchFuse kit (if required)Fuse kit (if required)
General ElectricType STDA Flange Disconnect SwitchVariable depth operating mechanismVariable depth operating mechanism
General ElectricType STDA Flange Disconnect SwitchDoor Hardware: n/aDoor Hardware: n/a
General ElectricType STDA Flange Circuit BreakerCircuit breakerCircuit breaker
General ElectricType STDA Flange Circuit BreakerHandle: STDA1XHandle: n/a
General ElectricType STDA Flange Circuit BreakerVariable depth operating mechanismVariable depth operating mechanism
General ElectricType STDA Flange Circuit BreakerDoor Hardware: n/aDoor Hardware: n/a
General ElectricCircuit Breaker w/SpectraFlexCircuit breakerCircuit breaker
General ElectricCircuit Breaker w/SpectraFlexFlange Mt. Handle: 150-600 amp, use STDA1X; SK1200, use STDA3XHandle: n/a
General ElectricCircuit Breaker w/SpectraFlexBreaker mounted mechanism.Breaker mounted mechanism.
General ElectricCircuit Breaker w/SpectraFlexOperating cableOperating cable
General ElectricCircuit Breaker w/SpectraFlexDoor Hardware: n/aDoor Hardware: n/a
I-T-E SiemensMax-Flex Flange Disconnect SwitchDisconnect switch: MCSDisconnect switch: MCS
I-T-E SiemensMax-Flex Flange Disconnect SwitchFuse Kit (if required)Fuse Kit (if required)
I-T-E SiemensMax-Flex Flange Disconnect SwitchHandle: Flange mount FHOHS4Handle: n/a
I-T-E SiemensMax-Flex Flange Disconnect SwitchSwitch operator mechanismSwitch operator mechanism
I-T-E SiemensMax-Flex Flange Disconnect SwitchOperating cable (standard 36.0”)Operating cable (standard 36.0”)
I-T-E SiemensMax-Flex Flange Disconnect SwitchDoor Hardware: n/aDoor Hardware: n/a
I-T-E SiemensMax-Flex Flange Circuit BreakerCircuit breakerCircuit breaker
I-T-E SiemensMax-Flex Flange Circuit BreakerPressure wire connectorsPressure wire connectors
I-T-E SiemensMax-Flex Flange Circuit BreakerHandle: Flange mount FHOH4Handle: n/a
I-T-E SiemensMax-Flex Flange Circuit BreakerCircuit breaker operator mechanismCircuit breaker operator mechanism
I-T-E SiemensMax-Flex Flange Circuit BreakerOperating cable: Standard 36"Operating cable: Standard 36"
I-T-E SiemensMax-Flex Flange Circuit BreakerDoor Hardware: n/aDoor Hardware: n/a
Square DClass 9422 Disconnect SwitchDisconnect switch and operating mechanism 9422Disconnect switch and operating mechanism 9422
Square DClass 9422 Disconnect SwitchHandle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2Handle: n/a
Square DClass 9422 Disconnect SwitchDoor Hardware: n/aDoor Hardware: n/a
Square DClass 9422 Circuit BreakerCircuit breakerCircuit breaker
Square DClass 9422 Circuit BreakerOperating mechanism: Class 9422Operating mechanism: Class 9422
Square DClass 9422 Circuit BreakerHandle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2Handle: n/a
Square DClass 9422 Circuit BreakerDoor Hardware: n/aDoor Hardware: n/a
Square DClass 9422 “T” Disconnect Switch w/ cable mechanismDisconnect switch and operating mechanism 9422, Type TDisconnect switch and operating mechanism 9422, Type T
Square DClass 9422 “T” Disconnect Switch w/ cable mechanismHandle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2Handle: n/a
Square DClass 9422 “T” Disconnect Switch w/ cable mechanismCable mechanism: Class 9422 CFT_O - 3, 5, or 10 footCable mechanism: Class 9422 CFT_O - 3, 5, or 10 foot
Square DClass 9422 “T” Disconnect Switch w/ cable mechanismDoor Hardware: n/aDoor Hardware: n/a
Square DCircuit Breaker w/cable mechanismCircuit breaker: Square DCircuit breaker: Square D
Square DCircuit Breaker w/cable mechanismHandle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2Handle: n/a
Square DCircuit Breaker w/cable mechanismDoor Hardware: n/aDoor Hardware: n/a

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8
Note:"K"=8.62when"C"=8.00
"K"=11.62when"C"=12.00
"P"=Wiring SpaceWiring SpaceWiring SpaceWiring SpaceWiring Space

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9col10
Fits Enclosure DepthFits Enclosure DepthABB Switch NumberAmpFuse ClassSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812ABB Switch NumberRatingFuse ClipFuse ClassLMPP
••OETL-NF30-F30ANo Fuse—4.453.7810.2813.28
••OETL-NF60-F60ANo Fuse—4.863.7810.0913.09
••OETL-NF100-F100ANo Fuse—4.864.789.5312.53
••OETL-NF175-F175ANo Fuse—7.306.497.2810.28
••OETL-NF200-F200ANo Fuse—7.367.287.2810.28
••OESA-F30J6-F30A30A-600VJ4.286.588.6111.61
••OESA-F60J6-F60A60A-600VJ4.286.268.6111.61
••OESA-F100J6-F100A100A-600VJ ¹6.547.658.1711.17
200A ²

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9
Fits Enclosure DepthFits Enclosure DepthAmpSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812ABB MechanismRatingFuse TypeLMPP
••FHD-M150AD6.923.949.1712.17
••FHF-M15A-225AE/Q5.984.237.7210.72
••FHF-M225AFrame7.444.237.7210.72
•FHJ-M400AJ9.715.62—8.77
•FHM-M600AL8.2811.26—8.28
•FHM-M800AM10.1111.26—7.87

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9col10
Fits Enclosure DepthFits Enclosure DepthISOMAX Circuit BreakerAmp RatingOperating MechanismFuse TypeSpace OccupiedSpace OccupiedWhen K=4.75When K=7.09
812ISOMAX Circuit BreakerAmp RatingOperating MechanismFuse TypeLMPP
••S1N100TL100AK2FHD-MS15.304.609.1312.13
•S3N150TW150AK3FHD-MS36.675.0211.53
•S3N225TW225AK3FHD-MS36.675.0211.53
•S4N250BW250AK4FHD-MS48.455.0210.00
•S5N400TW400AK5FHD-MS58.456.4010.00
•S6N600TW600AK6FHD-MS68.3310.009.33
•S6N800TW800AK6FHD-MS68.3310.009.33

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9col10
Fits Enclosure DepthFits Enclosure DepthAlan BradleyAmpSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812Type NumberRatingFuse ClipFuse ClassLMPP
••DS3030ANo Fuse—3.886.626.759.75
••DS3030A30A-250VH,K,R5.256.626.759.75
••DS3030A30A-600VH,K,R8.006.626.759.75
••DS3030A30A-600VJ5.256.626.759.75
••DS3030A60A-250VH,K6.006.626.759.75
••DS3030A60A-600VH,K8.506.626.759.75
••DS3030A60A-600VJ5.386.626.759.75
••DS6060ANo Fuse—3.886.626.629.62
••DS6060A60A-250VH,K,R6.006.626.629.62
••DS6060A60A-600VH,K,R8.506.626.629.62
••DS6060A60A-600VJ5.386.626.629.62
••DS6060A30A-600VH,K,R8.006.626.629.62
••DS6060A100A-250VH,K8.506.626.629.62
••DS6060A100A-600VH,K10.506.626.629.62
••DS6060A100A-600VJ7.256.626.629.62
••DS100¹100ANo Fuse—3.886.626.449.62
••DS100¹100A100A-250VH,K,R8.126.626.449.62
••DS100¹100A100A-600VH,K,R10.126.626.449.62
••DS100¹100A100A-600VJ6.886.626.449.62
••DS100¹100A60A-600VH,K,R10.126.626.449.62
••DS100¹100A60A-600VJ8.886.626.449.62
•DS200¹200ANo Fuse—4.757.88—8.12
•DS200¹200A200A-250VH,K,R10.887.88—8.12
•DS200¹200A200A-600VH,K,R13.387.88—8.12
•DS200¹200A200A-600VJ9.507.88—8.12
•DS200¹200A100A-600VH,K,R12.007.88—8.12
•DS200¹200A100A-600VJ8.757.88—8.12

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9
Fits Enclosure DepthFits Enclosure DepthAllen Bradley Type No.Amp RatingFuse TypeSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812Allen Bradley Type No.Amp RatingFuse TypeLMPP
••M4015A to 150AC-H Westinghouse Circuit Breakers EHD,FD,FDB,FDC,HFD,HMCP5.004.50¹8.12
••M4015A to 150AC-H Westinghouse Circuit Breakers EHD,FD,FDB,FDC,HFD,HMCP5.004.50¹8.1211.12
•M5070A to 250AC-H Westinghouse Circuit Breakers JD,JDB,JDC,HJD,HMCP9.754.75¹—
•M5070A to 250AC-H Westinghouse Circuit Breakers JD,JDB,JDC,HJD,HMCP9.754.75¹—10.62
•M60100A to 400AC-H Westinghouse Circuit BreakersKD,KDB,DK,HKD,HMCP9.696.12¹—
•M60100A to 400AC-H Westinghouse Circuit BreakersKD,KDB,DK,HKD,HMCP9.696.12¹—10.50

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9col10
Fits Enclosure DepthFits Enclosure DepthCutler HammerAmpSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812Type NumberRatingFuse ClipFuse ClassLMPP
••C361NC30ANo Fuse—5.757.437.3110.31
••C361SC2130A30A-250VH, K, R8.387.437.3110.31
••C361SC6130A60A-250VH, K, R8.387.437.3110.31
••C361SC6130A30A-600VH, J, K, R8.387.437.3110.31
••C361ND60ANo Fuse—5.757.437.3110.31
••C361SD2260A60A-250VH, K, R8.387.437.3110.31
••C361SD2260A30A-600VJ8.387.437.3110.31
••C361SD6260A30A-600VH, K, R8.387.437.3110.31
••C361SD6260A60A-600VJ8.387.437.3110.31
••C361NE100ANo Fuse—5.568.957.479.91
••C361SE263100A100A-250VH, K, R10.318.957.479.91
••C361SE263100A100A-600VH, K, R10.318.957.479.91
••C361SE263100A100A-600VJ10.318.957.479.91
¹ , ²²C361NF200ANo Fuse—13.0610.004.947.94
¹ , ²²C361SF264200A200A-250VH, K, R13.0610.004.947.94
¹ , ²²C361SF264200A200A-600VH, J, K, R13.0610.004.947.94

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9
Fits Enclosure DepthFits Enclosure DepthAllen Bradley Type No.AmpSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812Allen Bradley Type No.RatingFuse TypeLMPP
••C371E150AF Frame EHD,FDB,FD,HFD,FDC6.005.508.4411.44
••C371E150AF Frame HMCP6.005.508.4411.44
•C371F250AJ Frame JDB,JD,HJD,JDC8.948.00—11.25
•C371F250AJ Frame HMCP10.948.00—11.25
•C371F400AK Frame DK,KDB,KD,HKD9.758.00—10.75
•C371F400AK Frame HMCP9.758.00—10.75
•C371G600AL Frame LD,HLD,LDC8.4411.88—9.18
•C371G600AL Frame HMCP8.4411.88—9.18

Space Occupied by Disconnect

col1col2col3col4col5col6col7
Fits Enclosure DepthFits Enclosure DepthComplete OperatorComplete OperatorBreaker HeightBreaker Width
812MechansimAmp RatingFuse Type"X""Y"
••F1S03150AF Frame EHD,FDB,FD,HFD,FDC6.004.12
••F1S03150AF Frame HMCP6.004.12
••F2S03250AJ Frame JDB,JD,HJD,JDC10.004.12
••F2S03250AJ Frame HMCP10.004.12
••F3S03400AK Frame DK,KDB,KD,HKD10.125.50
••F3S03400AK Frame HMCP12.455.50
•F4S04600AL Frame LD,HLD,LDC10.758.25
•F7S04800AM Frame MD,MDS16.008.25
•F5S041200AN Frame ND,HND,NDC16.008.25
•F6S042500AR Frame RD,CRD, RDC16.0015.50

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9col10
Fits Enclosure DepthFits Enclosure DepthGeneral Electric Mechanism For SwitchAmp RatingSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812General Electric Mechanism For SwitchAmp RatingFuse ClipFuse ClassLMPP
••TDOM1A30ANo Fuse—7.75¹5.259.1212.12
••TDOM1A30A30A-250VH, R7.75¹5.259.1212.12
••TDOM1B30A30A-600VH, R12.38¹5.259.1212.12
••TDOM1B30A60A-250VH, R12.38¹5.259.1212.12
••TDOM1B30A60A-600VH, R12.38¹5.259.1212.12
••TDOM1A60ANo Fuse—7.75¹5.259.1212.12
••TDOM1B60A60A-250VH, R12.38¹5.259.1212.12
••TDOM1B60A60A-600VH, R12.38¹5.259.1212.12
••TDOM1B60A100A-250VH, R12.38¹5.259.1212.12
••TDOM1B60A100A-600VH, R12.38¹5.259.1212.12
••TDOM1A100ANo Fuse—7.75¹5.259.1212.12
••TDOM1B100A100A-250VH, R12.38¹5.259.1212.12
••TDOM1B100A100A-600VH, R12.38¹5.259.1212.12
••TDOM1B100A200A-250VH, R12.38¹5.259.1212.12
••TDOM1B100A200A-600VH, R12.38¹5.259.1212.12
••TDOM2200ANo Fuse—7.009.126.509.50
••TDOM2200A200A-250VH, R15.389.126.509.50
••TDOM2200A200A-600VH, R15.389.126.509.50

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9
Fits Enclosure DepthFits Enclosure DepthGeneral Electric Mechanism For SwitchAmp RatingSpace OccupiedSpace OccupiedWhen K=8.62When K=11.62
812General Electric Mechanism For SwitchAmp RatingFuse TypeLMPP
••SDOM1A150ATEB, TED, THED7.75¹5.259.0612.06
••SDOM1A150ATEC7.75¹5.259.0612.06
••TDOM1B150ATB112.38¹5.259.0612.06
••TDOM1B150ATEC, TECL12.38¹5.259.0612.06
••TDOM1C150ATEL7.75¹5.259.0612.06
••TDOM1D150ATHLC17.75¹5.256.629.62
••TDOM3225ATFJ10.385.757.6210.62
••TDOM3225ATFK, THFK, TFL10.385.757.6210.62
••TDOM4400ATJJ, TJK4, THJK4, TJL4V8.259.386.699.69
••TDOM4600ATJK6, THJK6, TJ4V, TJL4V8.259.386.699.69
••TDOM5400ATB4, TJH6S14.259.386.699.69
••TDOM6225ATLB2, THLC211.759.386.129.12
••TDOM6400ATLB4, THLC411.759.384.757.75
••SDOM1A150ASPECTRA SE1507.75¹5.259.0612.06
••SDOM3250ASPECTRA SF25010.385.757.0610.06
•SDOM4600ASPECTRA SG60010.007.00—7.93

Space Occupied by Disconnect

col1col2col3col4col5col6
Fits Enclosure DepthFits Enclosure DepthCircuit Breaker HeightCircuit Breaker Width
C=8C=12Frame SizeMax Amp RatingXY
••E150150A6.314.12
••SE150150A6.314.12
•SF250250A10.124.12
•SG600600A10.095.50
•SK12001200A15.508.25

Space Occupied by Disconnect

col1col2col3col4
Frame SizeBreaker MechanismFlange Mounting Handle¹Operating Cable²
E150SCOM1ASCH1SC3L
SE150/SF250SCOM1EFSCH1SC3L
SG600SCOM1GSCH1SC3L
SK1200SCOM1KSCH2KSC3H

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8
Fits Enclosure DepthFits Enclosure DepthAmp RatingDisconnect Height "X"Disconnect Width "Y"
C=8C=12SwitchAmp RatingFuse ClipFuse ClassDisconnect Height "X"Disconnect Width "Y"
••MCS603R30ANo Fuse—5.526.13
••MCS603R30A30A-250VH,K,R8.116.13
••MCS603R30A30A-600VH,K,R10.116.13
••MCS603R30A30A-600VJ8.486.13
••MCS606R60ANo Fuse—5.526.13
••MCS606R60A60A-250VH,K,R7.866.13
••MCS606R60A60A-600VH,K,R10.386.13
••MCS606R60A60A-600VJ8.366.13
••MCS610R100ANo Fuse—7.597.38
••MCS610R100A100A-250VH,K,R11.857.38
••MCS610R100A100A-600VH,K,R13.857.38
••MCS610R100A100A-600VJ10.607.38
••MCS620R200ANo Fuse—9.009.17
••MCS620R200A200A-250VH,K,R14.709.17
••MCS620R200A200A-600VH,K,R17.209.17
••MCS620R200A200A-600VJ13.329.17

Space Occupied by Disconnect

col1col2col3col4col5col6
Complete Operator MechansimBreaker Frame SizeCircuit Breaker TypeCircuit Breaker Height "X"Circuit Breaker Width "Y"
Complete Operator MechansimAmp RatingBreaker Frame SizeCircuit Breaker TypeCircuit Breaker Height "X"Circuit Breaker Width "Y"
FHOE036125AEDED2,ED4,ED6,HED4,HED6,6.343.00
FHOE036125ACEDCED69.583.00
FHOF036250AFDFXD6-A,FD6-A,HFD6,FXD6-ETJ,HHFD6, HHFXD69.504.50
FHOF036250ACFDCFD6,CFD6-ETI14.254.50
FHOJ036400A, 600AJD, LDJXD2,LXD6,JD6,LD6,HJD6,HLD6,HHJD6,HHLD6, HHJXD6,HHLXD6,JXD6-ETI,LXD6-ETI11.007.50
FHOJ036400A, 600ACJD,CLDCJD6,CLD6,CJD6-ETI,CLD6-ETI17.867.50
FHOLMO36800ALMDLMD6,LMXD6,HLMD6,HLMDX6,LMXD6-ETI16.009.00

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9col10
Fits Enclosure DepthFits Enclosure DepthAmp RatingSpace OccupiedSpace OccupiedWhen K=8.62 PWhen K=11.62 P
812Square D Type NumberAmp RatingFuse ClipFuse ClassLMWhen K=8.62 PWhen K=11.62 P
••TCN-3030ANo Fuse—3.806.847.5610.56
••TCF-3030A30A-250VH, K, R5.536.847.5610.56
••TCF-3330A30A-600VH, K, R8.156.847.5610.56
••TCF-3330A60A-250VH, K, R6.156.847.5610.56
••TCF-3330A30A-600VJ5.536.847.5610.56
••TDN-6060ANo Fuse—3.806.847.5610.56
••TDF-6060A30A-600VH, K, R8.156.847.5610.56
••TDF-6060A60A-250VH, K, R6.156.847.5610.56
••TDF-6360A60A-600VH, K, R8.656.847.5610.56
••TDF-6360A60A-600VJ5.536.847.5610.56
•TEN-10100ANo Fuse—3.806.847.4410.44
•TEF-10100A100A-250VH, K, R8.256.847.4410.44
•TEF-10100A100A-600VH, K, R10.256.847.4410.44
•TEF-10100A100A-600VJ7.056.847.4410.44
••TC-130ANo Fuse—5.756.006.629.62
••TC-230A30A-250VH, K, R5.756.006.629.62
••TC-330A30A-600VH, K, R7.756.006.629.62
••TC-330A60A-250VH, K, R5.886.006.629.62
••TC-330A30A-600VJ5.756.006.629.62
••TD-160ANo Fuse—6.386.627.5010.50
••TD-260A30A-600VH, K, R8.506.627.5010.50
••TD-260A60A-250VH, K, R6.506.627.5010.50
••TD-360A60A-600VH, K, R9.006.627.5010.50
••TD-360A60A-600VJ6.386.627.5010.50
•TE-1100ANo Fuse—4.758.38—10.25
•TE-2100A100A-250VH, K, R7.508.38—10.25
•TE-2100A100A-600VH, K, R9.508.38—10.25
•TE-2100A100A-600VJ6.258.38—10.25
•TE-3100A200A-600VJ13.758.38—10.25
•TF-1200ANo Fuse—5.5011.62—8.88
•TF-2200A200A-250VH, K, R11.5011.62—8.88
•TF-2200A200A-600VH, K, R14.0011.62—8.88
•TF-2200A200A-600VJ10.1211.62—8.88
•TF-3200A400A-600VJ14.5011.62—8.88

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8col9
Fits Enclosure DepthFits Enclosure DepthGeneral Electric Mechanism For SwitchAmp RatingSpace OccupiedSpace OccupiedWhen K=8.62 PWhen K=11.62 P
812General Electric Mechanism For SwitchAmp RatingFrame SizeLMWhen K=8.62 PWhen K=11.62 P
••RG-175AGJL3.533.747.4710.47
••RG-1100AGJL3.533.747.4710.47
••RN-1100AFAL,FHL5.125.257.6210.62
••RP-1250AKAL,KHL7.125.628.3811.38
•RR-1400ALAL, LHL, Q4L7.628.75—7.00

Space Occupied by Disconnect

col1col2col3col4col5col6col7col8
Fits Enclosure DepthFits Enclosure DepthSquare D Type NumberAmp RatingDisconnect Height "X"Disconnect Width "Y"
C=8C=12Square D Type NumberAmp RatingFuse ClipFuse ClassDisconnect Height "X"Disconnect Width "Y"
••TCN-3030ANo Fuse—5.906.20
••TCF-3030A30A-250VH, K, R7.506.20
••TCF-3330A30A-600VH, K, R10.156.20
••TCF-3330A60A-250VH, K, R8.156.20
••TCF-3330A30A-600VJ7.506.20
••TDN-6060ANo Fuse—5.906.20
••TDF-6060A30A-600VH, K, R10.156.20
••TDF-6060A60A-250VH, K, R8.156.20
••TDF-6360A60A-600VH, K, R10.656.20
••TDF-6360A60A-600VJ7.506.20
•TEN-10100ANo Fuse—5.906.20
•TEF-10100A100A-250VH, K, R10.356.20
•TEF-10100A100A-600VH, K, R12.356.20
•TEF-10100A100A-600VJ10.356.20

Space Occupied by Disconnect

col1col2col3col4col5col6col7
Fits Enclosure DepthFits Enclosure DepthAmpCircuit BreakerCircuit Breaker
C=8C=12Cable Type SwitchRatingFrame TypeHeight "X"Width "Y"
••9422 CGJ3075AGJL4.753.50
••9422 CEJ30100AGJL4.753.50
••9422 CFA30100AFAL,FHL6.004.50
••9422 CKA30250AKAL,KHL8.004.50
•9422 CLA30400ALAL,LHL,Q4L11.006.00